ESX10-115-DC24V-2A E-T-A Circuit Protection and Control, ESX10-115-DC24V-2A Datasheet - Page 2
ESX10-115-DC24V-2A
Manufacturer Part Number
ESX10-115-DC24V-2A
Description
CIRCUIT PROTECTOR; 2A CLASS I, DIVISION 2 ; CONTROL INPUT AND STATUS OUTPUT ; 24V
Manufacturer
E-T-A Circuit Protection and Control
Type
Electronicr
Datasheet
1.ESX10-101-DC24V-12A.pdf
(12 pages)
Specifications of ESX10-115-DC24V-2A
Actuator Type
Toggle
Brand/series
ESX10
Current, Rating
2 A
Mounting Type
Plug-In
Number Of Poles
1
Termination
Blade
Voltage, Rating
24 VDC
Lead Free Status / Rohs Status
RoHS Exempt Product
5
Status output SF
Electrical data
Status OUT
Status OUT
OFF condition
Signal output F
Electrical data
ON condition LED green
OFF condition LED off
Fault condition LED orange overload condition > 1.1 x I
Fault condition LED red
ESX10-101
ESX10-102
ESX10-103
ESX10-105/-106/-115/-125 group signal, make contact
Fault
5 - 28
Attention: when mounted side-by-side without convection the ESX10-0.. should not
current rating
I
Technical data
Table 1: voltage drop, current limitation, max. load current
N
0.5 A
1 A
2 A
3 A
4 A
6 A
8 A
10 A
12 A
carry more than 80 % of its rated load with 100 % ON duty due to thermal effects.
typically voltage drop active current
U
70 mV
80 mV
130 mV
80 mV
100 mV
130 mV
120 mV
150 mV
180 mV
ON
at I
N
Electronic Circuit Protector ESX10
(T ambient = 25°C, operating voltage U S = DC 24 V)
ESX10-104/-106/-124/-127
plus-switching signal output,
connects U
nominal data: DC 24 V / max. 0.2 A (short
circuit proof)
status output is internally connected to
GND with a 10 kOhm resistor
ESX10-104/-106/ -124 (signal status OUT),
at U
+24 V = S1 is ON, load output connected
through 0V = S1 is ON, load output
blocked and/or switch S1 is OFF
ESX10-127 (signal status OUT inverted),
at U
+24 V = S1 is ON, load output blocked,
red LED lighted
0 V = S1 is ON, load output connected
through and/or switch S1 is in OFF position
0 V level at status output when:
●
●
●
ESX10-101/-102/-103/-105/-106/-115/-125
potential-free signal contact
max. DC 30 V/0.5 A, min. 10 V/10 mA
voltage U
position
no overload, no short circuit
●
●
electronic disconnection
electronic disconnection upon
overload or short circuit
device switched off with control signal
(switch S1 is in ON position)
single signal, make contact
contact SC/SO-SI open
single signal, break contact
contact SC/SO-SI closed
group signal change-over contact
contact SC-SO open, SC-SI closed
contact SC-SO open
signal output fault conditions:
●
●
●
red LED lighted (electronic disconnection)
switch S1 is in ON position, but device is
still in switch-on delay
switch S1 is OFF, or control signal OFF,
device is switched off
no operating voltage U
device switched off
(switch S1 is in OFF position)
no voltage U
no operating voltage U
ON/OFF switch S1 is in OFF position
S
S
limitation (typically) T
= +24 V
= +24 V
1.8 x I
1.8 x I
1.8 x I
1.8 x I
1.8 x I
1.8 x I
1.5 x I
1.5 x I
1.3 x I
S
S
N
N
N
N
N
N
N
N
N
applied, switch S1 is in ON
to terminal 12 of module 17plus
S
applied
max. load current at 100 % ON duty
U
= 40 °C
0.5 A
1 A
2 A
3 A
4 A
6 A
8 A
10 A
12 A
S
S
N
up to
T
U
= 50 °C
0.5 A
1 A
2 A
3 A
4 A
5 A
7 A
9 A
10.8 A
www.e-t-a.com
Reset input RE
Electrical data
Reset signal RE
(= terminal 13,14 or 12
of Module 17plus)
Caution: unused slots
have to be fitted with
jumpers
Control input IN+
Electrical data
Control signal IN+
Switch S1 ON/OFF
General data
Fail-safe element:
Blade terminals
Housing
Mounting
Ambient temperature
Storage temperature
Humidity
Vibration
Degree of protection
EMC
(EMC directive, CE logo)
Insulation co-ordination
(IEC 60934)
dielectric strength
Insulation resistance
(OFF condition)
Approvals
Dimensions (W x H x D)
Mass
Technical data
(T ambient = 25°C, operating voltage U S = DC 24 V)
ESX10-124/-125/-127
voltage: max. + DC 32 V
high > DC 8 V ≤ DC 32 V
low ≤ DC 3 V > 0 V
power consumption typically 2.6 mA
(+DC 24 V)
min. pulse duration typically 10 ms
The electronically blocked ESX10-124/-127
may remotely be reset via an external
momentary switch due to the falling edge of
a +24 V pulse.
The reset signal will be fed in terminal 13, 14
or 12 of Module 17plus and is internally
pre-wired.
The reset simultaneously affects all blocked
ESX10-124/-127 channels of the power
distribution system, all switched on
ESX10-124/-127 channels remain
unaffected. With type ESX10-125 the reset
only affects the device concerned. By
connecting the individual terminals 12 of
the Module 17plus a joint reset signal for
all ESX10-125 may be generated.
ESX10-115
see reset input RE
+24 V level (HIGH): device will be switched
on by a remote ON/OFF signal
0 V level (LOW): device will be switched
off by a remote ON/OFF signal
unit can only be switched on with S1 if a
HIGH level is applied to IN+
backup fuse for ESX10 not required
because of the integral
redundant fail-safe element
6.3 mm to DIN 46244-A6.3-0.8
moulded
plug-in mounting utilising power distribution
system Module 17plus or SVSxx
0...+50 °C
(without condensation, see EN 60204-1)
-20...+70 °C
96 hrs/95 % RH/40 °C to
IEC 60068-2-78, test Cab.
climate class 3K3 to EN 60721
3 g, test to IEC 60068-2-6 test Fc
housing: IP30 DIN 40050
terminals: IP00 DIN 40050
emission: EN 61000-6-3
susceptibility: EN 61000-6-2
0.5 kV/2 pollution degree 2
re-inforced insulation in operating area
max. DC 32 V (load circuit)
n/a, only electronic disconnection
UL 2367, File # E306740
Solid State Overcurrent Protectors
UL 508, File # E322549
CSA C22.2 No: 14, File 16186
CE logo
12.5 x 70 x 60 mm
approx. 40 g
Issue C