EVT4-420-24L Eaton / Control Automation, EVT4-420-24L Datasheet - Page 2

no-image

EVT4-420-24L

Manufacturer Part Number
EVT4-420-24L
Description
AC VOLTAGE TRANSDUCER, 480 MAX INPUT, 4-20MA OUT, LOOP POWERED
Manufacturer
Eaton / Control Automation
Datasheet
P52215 Rev 02
292181021
TROUBLESHOOTING
SPECIFICATIONS
DIMENSIONS (in/mm)
Effective: 15 October 2009
Problem
Sensor has no output
Output signal is
too low
Sensor is always
at 4mA
Specifi cation
Power Supply
Input
Input Over-Range
Output
Response Time
Accuracy
Linearity
Loading
Isolation Voltage
Frequency Range
Operating Temperature
Enclosure
EMC/Immunity
Output Ripple
Approvals
2.66 (67.5)
3.53 (89.7)
1.77 (45)
Solution
Power supply is not properly sized. Check power supply voltage and
current rating.
Polarity is not properly matched. Check and correct wiring polarity.
Sensor model may be improperly sized for application. Determine the
normal operating voltage of your monitored circuit and ensure sensor
selected is equal to or slightly higher than the normal operating voltage.
Monitored load is not AC or is not on. Check that the monitored load is
AC and that it is actually on.
24V DC Loop-Powered
120V, 240V, and 480V
+15% of Nominal Range
4-20mA Propertional; Capped at 24mA Max.
250 ms (to 90% Value)
< 1%
< 0.5%
< 500 ohm
2,500V AC
40Hz - 5kHz
-30 to +60° C (-22 to +140° F), 0-95% Non-Condensing
UL94 V0 Rated
EN50081-1, EN50082-2
< 1% (Peak to Peak)
UL/CUL, CE Pending
1.40 (35.6)
2.39 (60.7)