S3K2U2200-5 SOLA HEVI DUTY, S3K2U2200-5 Datasheet
S3K2U2200-5
Specifications of S3K2U2200-5
Related parts for S3K2U2200-5
S3K2U2200-5 Summary of contents
Page 1
S3K2U UPS Version française, : reportez-vous www.solaheviduty.com/products/ups/UPSmanuals.htm. Para español, consulte www.solaheviduty.com/products/ups/UPSmanuals.htm. Die deutsche Fassung finden Sie auf www.solaheviduty.com/products/ups/UPSmanuals.htm. Per l'Italiano, consultare www.solaheviduty.com/products/ups/UPSmanuals.htm SER ANUAL Line-Interactive 1000 - 3000VA 230V ...
Page 2
...
Page 3
MPORTANT AFETY NSTRUCTIONS W S ICHTIGE ICHERHEITSANWEISUNGEN 1 LOSSARY OF YMBOLS 2 ...
Page 4
...
Page 5
Figure 1 Front view of UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 6
iv ...
Page 7
MPORTANT AFETY NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS and batteries. Please read this manual thoroughly before attempting to install or operate ...
Page 8
Your UPS provides conditioned power to connected equipment. This product is designed for Commer- cial use only not intended for use with life support and other designated “critical” devices. Maxi- mum load must not exceed that shown on ...
Page 9
W S ICHTIGE ICHERHEITSANWEISUNGEN DIESE ANWEISUNGEN AUFBEWAHREN Dieses Handbuch enthält wichtige Sicherheitsanweisungen, die während der Installation und Wartung der USV und Batterien befolgt werden sollten. Lesen Sie dieses Handbuch bitte gründlich durch, bevor Sie versuchen, diese USV zu installieren oder ...
Page 10
ACHTUNG ! Wenn Ihre USV einen der folgenden Zustände aufweist, muss die USV ausgeschaltet und der Netzstecker muss gezogen werden. Wenden Sie sich an Ihren örtlichen Händler, Sola/Hevi- Duty-Vertreter oder an den weltweiten Kundendienst von Sola/Hevi-Duty. • Das Netzkabel oder ...
Page 11
VORSICHT ! VORSICHTSMASSNAHMEN BEIM UMGANG MIT BATTERIEN Die Wartung von Batterien sollte von Personen, die sich mit Batterien und den erforderlichen Vorsichtsmaßnahmen auskennen, durchgeführt oder von solchen Personen überwacht werden. Unbefugtes Personal darf keinen Zugriff auf die Batterien erhalten. Bei ...
Page 12
G S LOSSARY OF YMBOLS Risk of electrical shock Gefahr eines Stromschlags Indicates caution followed by important instructions Zeigt einen Vorsichtshinweis an, auf den wichtige Anweisungen folgen Requests the user to consult the manual i Fordert den Benutzer dazu ...
Page 13
I NTRODUCTION Congratulations on your choice of the Sola/Hevi-Duty S3K2U Uninterruptible Power Supply (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission it may be ...
Page 14
Figure 2 1000 and 1440VA models—rear view Intellislot Port REPO INTELLISLOT USB Port RS232 (DB-9) Port Figure 3 2200 and 3000VA models—rear view Intellislot Input Circuit Port REPO Breaker REPO INTELLISLOT INPUT ...
Page 15
M C AJOR OMPONENTS Figure 4 Line diagram of S3K2U 1000VA & 1440VA Input EMI/RFI Filter Charger G Figure 5 Line diagram of S3K2U 2200VA & 3000VA Input EMI/RFI Filter Charger G 3.1 Transient Voltage Surge Suppression (TVSS) and ...
Page 16
Automatic Voltage Regulator The Automatic Voltage Regulator (AVR) protects connected equipment from power spikes, sags and other abnormalities by raising (boosting) or lowering (bucking) the output voltage as needed. This keeps the UPS output voltage within the connected equipment’s ...
Page 17
W ’ I HAT S NCLUDED The S3K2U unit is shipped with the following items: • S3K2U user manual • Warranty Card • MultiLink serial cable (black), 3m (10 ft) • Contact Closure Cable (gray), 3m (10 ft) • ...
Page 18
I NSTALLATION 5.1 Preparation 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local distributor, Sola/Hevi-Duty representative or Sola/Hevi-Duty Technical Services. CAUTION ! The UPS is heavy (see Table 5 - Battery cabinet ...
Page 19
Figure 7 Rack mount handles Two (2) M4x6 Flat Head Screws 2. Unpack the two fixed rail assemblies and mounting hardware. Loosen the wing nuts and extend the inner members to their outermost position (see Figure 8). Figure 8 Fixed ...
Page 20
Figure 9 Rack mounting rails and slide assemblies Lay the UPS in rack-mounting position on the fixed rails. The UPS should move smoothly forward and backward on the fixed rails. If not, recheck alignment. CAUTION ! Lifting ...
Page 21
Connect Phone/Fax/DSL/Network/Modem devices to data line connectors. RJ11/RJ45 connection INPUT IN OUT BREAKER PUSH TO RESET 1 2 LOAD PHONE / FAX / MODEM / NETWORK PROTECTION INPUT LOAD 2 INTELLISLOT 16. Communication options (see 8.0 ...
Page 22
Figure 10 REPO switch connections REPO Connector REPO Switch as shipped Key to REPO switch connections 1. 24 VDC 2. Sense 3. Sense REPO connections for normally open switch system Installation ...
Page 23
External Battery Cabinet Installation Optional Sola/Hevi-Duty external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath ...
Page 24
C I ONTROLS AND NDICATORS All indicators illuminated for illustrative purposes only. 6.1 ON/Alarm Silence/Battery Test Button This button controls output power to connected load(s) and has three functions: •On •Alarm Silence •Battery Test ON—When the UPS is Off, ...
Page 25
Voltage Programming Button The S3K2U contains a Voltage Programming button that allows the operator to select the nominal mains voltage. This setting changes the mains transfer points (low and high) of the UPS and the nominal output voltage when ...
Page 26
Over Temp Indicator—Amber The Over Temp Indicator flashes when the UPS detects an over temperature condition. This indicator illuminates when the UPS shuts down due to an over temperature condition (see 11.0 - Trouble- shooting for details). 6.10 Fault ...
Page 27
M O ODES OF PERATION 7.1 Normal Mode During Normal mode operation, the S3K2U supplies conditioned, computer-grade power to the con- nected equipment: mains power passes through the TVSS circuitry and the EMI/RFI filters and then through the Inverter ...
Page 28
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 15 shows the UPS in Battery mode with 61% - 80% battery capacity ...
Page 29
C OMMUNICATIONS 8.1 DB-9 Connector The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer system running MultiLink software. The DB-9 is capable of supplying serial communica- tion, on ...
Page 30
USB Interface Port The S3K2U has a USB interface port for communication that will work with the built-in Microsoft Power Manger software on the user’s PC equipped. It will provide UPS status and manages the automatic orderly ...
Page 31
V P OLTAGE ROGRAMMING Figure 17 Load Level Indicators Voltage Programming Button 1. Remove the front bezel from the UPS. 2. UPS must be operating in Normal (AC) mode. NOTE Mains power will be applied to the connected load. ...
Page 32
M AINTENANCE The S3K2U UPS requires very little maintenance. Follow these practices to prevent problems. 10.1 Cleaning the UPS The following will help ensure trouble-free operation for years: • Vacuum dust from the ventilation intake occasionally. • Wipe the ...
Page 33
VORSICHT ! Bei einer Batterie ist das Risiko eines Stromschlags und eines starken Kurzschlussstroms gegeben. Folgende Vorsichtsmaßnahmen sollten beim Austausch der Batterien beachtet werden: • Armbanduhren, Ringe und sonstige Metallobjekte sind zu entfernen. • Verwenden Sie einen Kreuzschlitzschraubendreher mit isoliertem ...
Page 34
Internal Battery Replacement Procedure (Verfahren zum Austausch von internen Batterien) 1. Gently remove the front plastic bezel cover from the UPS. (Demontieren Sie die vordere Kunststoffblendenabdeckung vorsichtig von der USV.) 2. Loosen and remove the five (5) screws on ...
Page 35
T ROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the S3K2U experiences a problem. Use this information to determine whether external factors caused the prob- lem. See Table 3 - Troubleshooting chart for ...
Page 36
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 5.0 - Installation. If the problem persists, refer to Table 3: Table 3 Troubleshooting chart Problem UPS will not start Short circuit Battery disconnected ...
Page 37
... Off <50 dBA, internal fan( Specifications (Sechnische Daten) S3K2U2200-5 S3K2U3000-5 2200VA/1650W 3000VA/2250W 87 x 612 x 430 87 x 612 x 430 (3.43 x 24.1 x 17) (3.43 x 24.1 x 17) ...
Page 38
... Up to 3,000m (10,000 ft) at 35°C (95°F) without derating EN 62040-1-1; TUV/GS listed; CE compliance mark EN 50091-2, Class B ISTA Procedure 1A Certification 32 Specifications (Sechnische Daten) S3K2U2200-5 S3K2U3000-5 S3K72BAT S3K2U2200-5 S3K2U3000 612 x 430 (3.43 x 24.1 x 17) 333 x 864 x 598 (13 23.5) 46 (101.4) 53.6 (118.1) 2 strings 12V x 9Ah ...
Page 39
Table 6 Battery run times Load% Internal 5% Battery 10% (minutes) 20% 30% 40% 50% 60% 70% 80% 90% 100% Internal 5% Battery + 1 10% External Battery 20% Cabinet 30% (minutes) 40% 50% 60% 70% 80% 90% 100% Internal ...
Page 40
... S3K2U1440-5 S3K2U2200-5 1440VA/1080W 2200VA/1650W 87 x 557 x 430 87 x 612 x 430 (3, 17) (3,43 x 24,1 x 17) 300 x 706 x 598 333 x 864 x 598 (11,8 x 27,8 x 23,5) (13 23,5) 31,0 (68,2) 35,0 (77,0) 39,0 (85,8) ...
Page 41
... CSB, B&B Battery und EnerSys Siehe Tabelle 5 - Batterielaufzeiten °C bis +40 °C (+32 °F bis +104 °F) -15 °C bis +40 °C (+5 °F bis +104 ° bis 95 %, nicht kondensierend ohne Leistungsminderung 35 Specifications (Sechnische Daten) S3K2U2200-5 S3K2U3000-5 (8) IEC-320-C13 (8) IEC-320-C13 (1) IEC-320-C19 (1) IEC-320-C19 6 x 12V x 7Ah 6 x 12V x 9Ah Bis zu 3.000m (10.000 ft) bei 35 ° ...
Page 42
... Bis zu 3.000m (10.000 ft.) bei 35 °C (95 °F) ohne Leistungsminderung EN 62040-1-1; TÜV/GS-Liste; CE-Konformitätsmarkierung EN 50091-2, Klasse B Zertifizierung nach ISTA-Verfahren 1A 36 Specifications (Sechnische Daten) S3K2U2200-5 S3K2U3000-5 S3K72BAT S3K2U2200-5 S3K2U3000 612 x 430 (3,43 x 24,1 x 17) 333 x 864 x 598 (13 23,5) 46 (101,4) 53,6 (118,1) 2 Stränge mit ...
Page 43
Product Warranty Registration To register for warranty protection: Technical Support • Visit the http://www.solaheviduty.com/support/index.htm • Click on the Warranty link and fill in the form. This will register your product with Sola/Hevi- Duty. For UPS purchasers: The MultiLink software ...
Page 44
Specifications (Sechnische Daten) 38 ...
Page 45
...
Page 46
Technical Support U.S. (800) 377-4384 International . . . . . . . . . . ...