S3K2U1000-5 SOLA HEVI DUTY, S3K2U1000-5 Datasheet - Page 16

UPS - Uninterruptible Power Supplies 1000VA/750W 230V

S3K2U1000-5

Manufacturer Part Number
S3K2U1000-5
Description
UPS - Uninterruptible Power Supplies 1000VA/750W 230V
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of S3K2U1000-5

Power Rating
1000 VA
Output Voltage Rating
230 V
Number Of Outlets
8
Interface Port
USB / SNMP
Runtime (full Load)
5 min
Runtime (half Load)
12 min
Topology
Line Interactive
Tower / Rackmount
Tower / Rackmount
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
3.3
3.4
3.5
3.6
3.7
3.8
Automatic Voltage Regulator
The Automatic Voltage Regulator (AVR) protects connected equipment from power spikes, sags and
other abnormalities by raising (boosting) or lowering (bucking) the output voltage as needed. This
keeps the UPS output voltage within the connected equipment’s tolerance and accommodates wide
mains voltage fluctuations without utilizing the batteries.
Battery Charger
In Normal mode, the Battery Charger converts mains AC power into regulated DC power to float
charge the battery. It is continuously charging the battery whenever the UPS is plugged into a power
outlet and mains power is within acceptable limits - even if the UPS is turned Off.
Battery
The S3K2U utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life,
operate the UPS in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery
cabinets are available to extend battery run times.
Inverter—1000/1440 Models Only
In battery mode operation, the inverter utilizes the DC output of the battery and inverts it into pre-
cise, regulated, sinewave AC power.
DC-to-DC Converter—2200/3000 Models Only
The DC-to-DC Converter utilizes energy from the battery system and raises the DC voltage to the
optimum operating voltage for the Bi-Directional Converter. This allows the Bi-Directional Converter
to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
Bi-Directional Converter—2200/3000 Models Only
In normal operation, the Bi-Directional Converter changes mains AC power into regulated DC power
to “float charge” the battery system. This converter is continuously charging the battery whenever the
UPS is plugged into a power outlet and mains power is within acceptable limits—even if the UPS is
turned Off. When mains power fails, the Bi-Directional Converter draws energy from the battery
through the DC-to-DC Converter and inverts it into a regulated sinewave supplying power to con-
nected equipment.
10
Major Components

Related parts for S3K2U1000-5