DLRO10X-NIST Megger, DLRO10X-NIST Datasheet - Page 3

no-image

DLRO10X-NIST

Manufacturer Part Number
DLRO10X-NIST
Description
Digital Multimeters DIGITAL LOW RESISTNC ENHANCED 10 AMP W/CR
Manufacturer
Megger
Datasheet

Specifications of DLRO10X-NIST

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Measurement:
Display:
Test Method:
Test Current:
Maximum Lead Resistance:
Voltmeter input impedance:
Hum rejection:
Data:
Battery:
Charging Rate:
Temperature:
Storage
Humidity (max):
Altitude (max):
Safety:
EMC:
Dimensions:
Weight:
Full Scale
1.9999 mΩ
19.999 mΩ
199.99 mΩ
1.9999 Ω
19.999 Ω
199.99 Ω
1999.9 Ω
Range and Safety:
Slow charging:
Measurement:
Co-efficient:
Memo Field
Resolution
0.1 µΩ
1 µΩ
10 µΩ
100 µΩ
1 mΩ
10 mΩ
100 mΩ
Operation:
Recharge:
Accuracy:
Standard:
Capacity:
Stability:
Transfer:
Control:
Storage:
Speed:
Mode:
Life:
Accuracy*
±0.2% ±0.2µΩ
±0.2% ±2 µΩ
±0.2% ±20 µΩ
±0.2% ±0.2 mΩ
±0.2% ±2 mΩ
±0.2% ±20 mΩ
±0.2% ±0.2 Ω
D D L L R R O O 1 1 0 0
Manual, Auto, Continuous,
High Power
Fully Automatic
<3s for forward & reverse current and to display average
41/2 digit seven segment LED
LED indication
Single cycle reversing d.c. ratiometric measurement -average result display.
±10%
<10 ppm per second
100 mΩ total for 10A operation irrespective of battery condition.
> 200 kΩ
Less than 1% ±20 digits additional error with 100 mV peak 50/60 Hz. on the potential leads. Warning
will show if hum or noise exceeds this level.
7 Ah NiMH rechargeable
Typically 1000 x 10 A tests before recharge
Via External 90V - 260V 50/60 Hz charger or from 12 to 15V d.c. supply
2.5 hours to 90% capacity, 4 hrs for full charge
+5ºC to +45ºC (41ºF to 113ºF) at full specification
-10°C to +50°C (14°F to 122°F) at reduced accuracy
-30ºC to +70ºC (-22ºF to 158ºF)
<0.01% per ºC over range 5ºC to 40ºC (<0.006% per ºF from 41ºF to 104ºF)
+10°C to +45°C (50°F to 113°F)
90% RH @ 40ºC (104ºF) non-condensing
2000m (6562 ft) to full safety specifications
In accordance with IEC61010-1 600V Category III - only when DH6 leads are used
In accordance with IEC61326-1
220 x 100 x 237 mm (8.6 x 4 x 9.5 in)
2.6 kg (5 3/4 lb.) including battery module.
* The accuracy stated assumes forward and reverse measurements.
Inductive mode or undirectional mode will introduce an undefined error if an external EMF is present.
Resistive
20 mV
20 mV
20 mV
20 mV
20 mV
20 mV
200 mV
Full Scale Volts
Inductive
n/a
20 mV
200 mV
200 mV
200 mV
200 mV
200 mV
Manual, Auto, Continuous,
High Power, Unidirectional
Fully Automatic/Manual
Large backlit LCD
Real Time or from storage via RS232
700 tests
Up to 200 characters per test via integral
alphanumeric keypad
Resistive
10 A
1 A
100 mA
10 mA
1 mA
100 µA
100 µA
DLRO 10 AND DLRO 10X
Test Current
Inductive
n/a
1 A
1 A
100 mA
10 mA
1 mA
100 µA
D D L L R R O O 1 1 0 0 X X
Digital Microhmmeter