565 AEMC, 565 Datasheet

LEAKAGE CURRENT METER, CLAMP, 4-DIGIT

565

Manufacturer Part Number
565
Description
LEAKAGE CURRENT METER, CLAMP, 4-DIGIT
Manufacturer
AEMC
Datasheet

Specifications of 565

Dmm Type
Clamp
Voltage Measuring Range Dc
0V To 600V
Voltage Measuring Range Ac
0V To 600V
Current Measuring Range Ac
0A To 100A
Resistance Measuring Range
1k Ohm
Rohs Compliant
NA

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
565-002-000-310
Manufacturer:
EDAC Inc.
Quantity:
4 120
Part Number:
565-002-000-311
Manufacturer:
EDAC Inc.
Quantity:
4 139
Part Number:
565-002-000-410
Manufacturer:
EDAC Inc.
Quantity:
44
Part Number:
565-002-000-411
Manufacturer:
EDAC Inc.
Quantity:
116
Part Number:
565-003-000-310
Manufacturer:
EDAC Inc.
Quantity:
1 555
TRMS Leakage Current Meter
Model 565
The TRMS Clamp-On Leakage
Current Meter Model 565 is designed
to measure low AC currents, which are
typically leakage currents in ground
conductors. Low currents are
measured using either the 60mA or
the 600mA range. The high sensitivity
of the probe (10µA and 100µA) is
possible through special jaw
construction and, in particular, critical
shielding of the jaws. At low measure-
ment levels, this shielding out of the
noise is critical for low sensitivity,
accuracy and stability.
Technical Assistance (800) 343-1391
Leakage current may be measured on
a ground conductor and through the
vector sum on multi-conductors. On a
grounded system, clamp around the
two or three conducting legs (not the
ground conductor). The vector sum of
the load currents will cancel out, leaving
the leakage current measured.
The Model 565 may be used as a
standard clamp-on meter measuring
to 100Arms, as well as V
resistance and continuity (with
a buzzer). In mA
low-pass filter, which will ignore all
AC
and A
AC
AC
, a
and V
DC
,
harmonic currents, can be activated.
In this mode, only the fundamental
signal is measured. The difference
between the full frequency signal
(WIDE displayed on LCD) and Filtered
mode (50/60Hz displayed on LCD)
essentially corresponds to the current
attributable to harmonics.
The Model 565 is ergonomic in design
and fits well in the hand, facilitating
one hand operation. The jaw size is
compact yet designed to accommodate
the most common conductors up to
1" (26mm) in diameter.
TRMS Leakage Current Meter Model 565
www.aemc.com
1 of 5
04/05

565 Summary of contents

Page 1

... The vector sum of the load currents will cancel out, leaving the leakage current measured. The Model 565 may be used as a standard clamp-on meter measuring to 100Arms, as well as V and V AC ...

Page 2

... Process loop monitoring • General AC load monitoring • Industrial troubleshooting Measuring leakage current on a ground wire with the TRMS Leakage Current Meter Model 565 Jaw Opening: 1.10" (28mm) Conductor Size: 1" (26mm) TRMS Leakage Current Meter Model 565 www.aemc.com 04/05 ...

Page 3

... LED with 180 sec Auto-Off 32° to 104°F (0° to 40°C); < 80% RH (non-condensing) 14° to 140°F (-10° to 60°C); < 70% RH (non-condensing) EN 61010-1 Ed. 2001, EN 61010-2-032 Ed. 2003, 600V, Cat. III Yes Yes V-Hz 0.1Hz 1Hz 5Vrms min TRMS Leakage Current Meter Model 565 04/05 www.aemc.com ...

Page 4

... Typical Points for Measuring Leakage Current On single phase systems, the Model 565 will measure leakage current at the source, the load or the ground. ORDERING INFORMATION TRMS Leakage Current Meter Model 565 (TRMS, 100A, 600V Technical Assistance (800) 343-1391 Construction Jaw opening: 1.10" (28mm) Conductor size: 1" ...

Page 5

... Faraday Drive Dover, NH 03820 USA (978) 526-7667 • Fax (978) 526-7605 export@aemc.com www.aemc.com All other countries: Chauvin Arnoux SCA 190, rue Championnet 75876 Paris Cedex 18, France • Fax info@chauvin-arnoux.com www.chauvin-arnoux.com Technical Assistance (800) 343-1391 TRMS Leakage Current Meter Model 565 04/05 www.aemc.com ...