H-TRIO-02 (Thermal Relay Input/Output)
The H-TRIO-02 provides four form C alarm contacts and 4 temperature probes on a
convenient rear shelf mounted single card. This option can work with or without the NIC. If
only the H-TRIO-02 is equipped on the shelf without a NIC option, three alarms are available
from the relay connector; DC Fail, AC Fail, and Fuse Alarm. In this configuration the
temperature probes are inactive. When the H-TRIO-02 and the NIC are both installed in a
system, 4 alarms are available on the relay connector and these may be mapped through the
NIC in any configuration. Additionally the temperature probes will be active.
HC Display
For systems that are configured with a DC distribution door, a display function is available.
This option will provide a convenient way to view and/or change set points, alarms, and
thermal compensation. As noted in Table 2, the HC display option is currently available on the
HK shelf family.
Table 6 – NIC Controller Parameters (Profile A01)
System Parameters
Audible
Relay Test
Password
* - Requires LVD & proper shunt
** - Requires LVD
When any alarm is selected, Audible
alarm will sound if any alarm is present.
When MJR or MNR is selected, audible
alarm will sound if any MJR, or MNR
alarm is present. When minor is
selected, audible alarm will sond if any
minor alarm is present. When major
alarm is selected, audible alarm will
sound if any major alarm is present. If
disabled has been selected, audible
alarm will not sound if any alarm is
present.
Enables or disables the Relay Test.
When Enabled, Relays A- F can be
tested, by setting the relay condition as
active or inactive.