Mounting Racks
48
The following figure shows a side view of a mounted CPU and two Expansion I/O
Racks. There should be a distance of 70 to 120 mm between the Racks. The
total length of I/O cables connecting any one series of Expansion I/O Racks
must be 50 m or less.
Do not mount the PC in a control panel in which high-power equipment is in-
stalled and make sure the point of installation is at least 200 mm away from pow-
er lines as shown in the following diagram. Ensure the plate to which the PC is
mounted is grounded.
Approx. 100 mm
Power lines
200 mm min.
PC
CPU
Duct
Duct
I/O
I/O
200 mm min.
70 to 120 mm
70 to 120 mm
Section 3-3