Analog Output Terminals
User Adjustment
Setting Using the DeviceNet Configurator
372
1,2,3...
Depending on factors such as the characteristics and connection methods of
the output device, the output can be adjusted to compensate for error in the
final output. The following diagram shows when compensation is applied to
the conversion line at the two points for 0% and 100%.
The ranges supported for adjustment (–5% to +5%) are shown in the following
table. If adjustment cannot be performed within the following ranges, check
the method being used to connect the output device.
1. Double-click the icon of the Analog Slave to be set in the Main Window and
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
0%
Output range
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
Conversion data
–0.25 to 0.25 V
0.8 to 1.2 V
–0.5 to 0.5 V
–11 to –9.0 V
3.2 to 4.8 mA
0.2 to 1.0 mA
Low Limit
100%
After adjustment
Before adjustment
Voltage/current
4.75 to 5.25 V
4.8 to 5.2 V
9.5 to 10.5 V
9.0 to 11 V
19.2 to 20.8 mA
19 to 21 mA
High Limit
Section 7-5