Analog Input Terminals
User Adjustment
Setting Using the DeviceNet Configurator
352
1,2,3...
Off-wire Detection functions with input ranges of 1 to 5 V or 4 to 20 mA only.
With the 1 to 5 V input range, an off-wire condition is detected when the input
voltage is below 0.76 V (less than 6%). With the 4 to 20 mA input range, an
off-wire condition is detected when the input current is below 3.04 mA.
Depending on factors such as the characteristics and connection methods of
the input device, the input can be adjusted to compensate for error in the input
voltage or current. The following diagram shows when compensation is
applied to the conversion line at the two points for 0% and 100%.
The following table shows the input ranges that support user adjustment.
1. Double-click the icon of the Analog Slave to be set in the Main Window and
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
0%
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
Input range
Conversion data
–0.25 to 0.25 V
0.8 to 1.2 V
–0.5 to 0.5 V
–11 to –9.0 V
3.2 to 4.8 mA
–1.0 to 1.0 mA
Low Limit
100%
Before adjustment
After adjustment
Voltage/current
4.75 to 5.25 V
4.8 to 5.2 V
9.5 to 10.5 V
9.0 to 11 V
19.2 to 20.8 mA
19 to 21 mA
High Limit
Section 7-4