EG1R-VM EDWARDS SIGNALING PRODUCTS, EG1R-VM Datasheet - Page 4

no-image

EG1R-VM

Manufacturer Part Number
EG1R-VM
Description
20H6033
Manufacturer
EDWARDS SIGNALING PRODUCTS
Datasheet
dBA output
Notes
1. All values shown are dBA measured at 10 feet (3.01m).
2. UL464 values measured in reverberant room.
3. Average and Peak values are measured in anechoic chamber.
Specifications
Page 4 of 6
Housing
Lens
Mounting
(indoor only)
Wire connections
Operating environment
Agency listings/approvals
Dimensions (HxWxD)
Operating voltage
Strobe output rating
Strobe flash rate
Synchronization Sources
Horn pulse rate
Temporal audible pattern
Temporal Horns, Horn-strobes (EG1-HD, EG1-HDVM
series)
High
dB
Setting
16 Vdc
24 Vdc
33 Vdc
Low dB
Setting
16 Vdc
24 Vdc
33 Vdc
Steady Tone Horns (EG1-P series)
16 Vdc
16 Vfwr
Temporal
Temporal
81.4
84.4
86.3
76.0
79.4
82.1
77 dBA, min
77 dBA, min
UL464
UL464
UL464
Steady
Steady
Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating.
Optical grade polycarbonate (clear)
Strobes and horn-strobes are for wall-mount installation only. Horn-only models may be ceiling- or wall-mounted.
Flush mount: 2½ inch (64 mm) deep one-gang box
Surface mount: Model 27193 surface mount box, wiremold box, or equivalent surface-mount box
With optional trim plate: One-gang, two-gang, four-inch square, octagonal, or European single-gang box
Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size
Indoor only: 32-120°F (0-49°C) ambient temperature. 93% relative humidity
UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CSFM, CE, FCC, MEA.
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.)
Signal: 4-1/2” x 2-3/4” x 13/16” (113 mm x 68 mm x 21 mm)
Trimplate: 5” (127 mm); Height – 5-7/8” (149 mm); Depth – ½” (13 mm)
EG1-HD series temporal-tone horns: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded when horn
set to steady tone)
EG1-HDVM series temporal-tone horn-strobes: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded
(audible NAC only) when used with optional EG1M Genesis Signal Master)
EG1-VM series strobes: non-coded, filtered 16 - 33 Vdc or unfiltered 16-33 Vdc FWR
EG1-P series steady-tone horns: coded or non-coded, filtered 20-31 Vdc or unfiltered 20-27 Vfwr
UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output
UL 1971: 15 cd (fixed 15/75 cd models)
UL 1638, ULCS526: 75 cd (fixed 15/75 cd models)
EG1-VM strobes and EG1-HDVM series temporal-tone horn-strobes: one flash per second synchronized with optional
EG1M Genesis Signal Master indefinitely within 10 milliseconds. Temporal setting (private mode only): synchronized to
temporal output of horns on same circuit
EG1M-RM, EBPS6A, EBPS10A, E-FSA64, E-FSA250, E-FSC 3, 5 and 10 zone.
EG1-HD temporal-tone horns and EG1-HDVM series temporal-tone horn-strobes: temporal rate synchronized with
optional EG1M Genesis Signal Master indefinitely within 10 milliseconds. EG1-P steady-tone horns: continuous, steady
tone only
½ sec ON, ½ sec OFF, ½ sec ON, ½ sec OFF, ½ sec ON, 1½ sec OFF, then repeat cycle
85.5
88.6
90.4
80.1
83.5
86.5
Temporal/
Temporal/
Average
Average
Average
Steady
Steady
85 dBA
85 dBA
91.4
94.5
96.9
86.3
89.8
92.5
Temporal/
Temporal/
Steady
Steady
91 dBA
91 dBA
Peak
Peak
Peak
94.2
97.6
99.5
89.2
92.5
95.3
Average Sound Output (dBA)
Light output - (effective cd)
-90°
-75°
-75°
(High dB setting, anechoic, 24V, measured at 10ft)
120
-60°
-60°
120
110
110
100
100
-45°
-45°
90
90
Percent of UL rating versus angle
80
80
70
-30°
-30°
Not to be used for installation purposes.
70
60
60
50
50
40
40
-15°
-15°
30
30
20
Per Cent of UL Rating
D A T A S H E E T
20
10
10
dBA
0
0
10
10
20
20
30
30
15°
15°
40
40
50 60
50 60
30°
30°
70
70
S85001-0573
80 90 100 110 120
80 90 100 110 120
45°
45°
60°
60°
75°
75°
90°
90°
Issue 11