FLLD3025AAB01 Kemet Corp, FLLD3025AAB01 Datasheet

no-image

FLLD3025AAB01

Manufacturer Part Number
FLLD3025AAB01
Description
Chassis Mount Filters - Motor Drive Filters
Manufacturer
Kemet Corp
Datasheet
Chassis Mount Filters - Motor Drive Filters
Filter Range
* other variants on request
Three phase and neutral - high performance
This three phase and neutral fi lter series provides a high
level of attenuation across a broad frequency spectrum.
The fi lter housing`s small footprint and option of fl ange
of M5 captive nut mounting, ensures ease of installation
within manufactures original equipment. The AB series is
particularly suited for UPS, switch mode power supplies,
industrial control systems and other such applications.
Mechanical Specifi cations
Manufacture:
Connections:
FLLD3 series
AB type
Code
FLLD3025AAB01
FLLD3036AAB01
FLLD4036AAB03
FLLD3050AAB01
FLLD4050AABR3
FLLD3063AAB01
FLLD3063AAB08
Approvals
Current ratings from 25A to 63A
Choice of performance options
High symmetric and asymentric attenuation
Screw or terminal block connectors
Compact enclosure styles
Captive nut or fl ange mounting designs
I
(A)
25
36
36
50
50
63
63
R
L
(mH)
4x1.2
4x0.95
4x1.3
4x2.0
4x0.5
4x0.7
4x0.7
tin-plate case with captive nut M5 for
mounting, on D3025A, 36A, 50A, 63A
with mounting fl anges on D4036A, 50A
electrical components sealed with resin.
threaded bar with metric nut M6;
D4036A with terminal blocks to accept
10mm
D4050A with terminal blocks to accept
25mm
1
Made in accordance to VDE, UL and CSA requirements
Cx
(µF)
3x2.2
3x2.2
3x2.2
3x2.2
3x2.2
3x2.2
3x2.2
2
2
1
cable.
cable.
Cx
(µF)
3x2.2 2x15000
3x2.2 2x15000
3x2.2 2x15000
3x2.2 2x15000
3x2.2 2x22000 3x4700
3x2.2 2x15000
3x2.2 2x15000
2
Cy
(pF)
1
Cy
(pF)
2
I
(mA)
<3.2
<3.2
<3.2
<3.2
<6.1
<3.2
<3.2
L
R
(M )
3x0.47
3x0.1
3x0.1
3x0.47
3x0.1
3x0.47
3x0.47
Case
B
A
D
B
E
B
C
1
Electrical Specifi cations
Rated voltage (V
Rated current (I
Leakage current (I
Voltage test (2 s.):
Climatic category:
R
):
R
): max 440V (ph-ph), 50/60Hz
L
): at V
referred to room temperature = 40°C
line to ground 2700Vdc
line to line 1075Vdc
Temperature range: -25°C to +85°C
HPF (25/085/21);
R
/ √ 3, 50Hz, max value
AB type
FLLD series
11/2009

Related parts for FLLD3025AAB01

FLLD3025AAB01 Summary of contents

Page 1

... D4050A with terminal blocks to accept 25mm cable. 2 Filter Range FLLD3 series type (A) (mH) (µF) (µF) (pF) Code FLLD3025AAB01 25 4x1.2 3x2.2 3x2.2 2x15000 FLLD3036AAB01 36 4x0.95 3x2.2 3x2.2 2x15000 FLLD4036AAB03 36 4x1.3 3x2.2 3x2.2 2x15000 FLLD3050AAB01 50 4x2.0 3x2.2 3x2.2 2x15000 FLLD4050AABR3 50 4x0.5 3x2 ...

Page 2

Chassis Mount Filters - Motor Drive Filters Insertion loss (typical): Asymmetrical (line to ground) ___ ...025AAB01, _.._.._ ...036AAB- -, _._._ ...050AAB01 ...063AAB- - Insertion loss (typical): Asymmetrical (line to ground) ... D4050AABR3 Insertion loss (typical): Symmetrical (line ...

Page 3

Chassis Mount Filters - Motor Drive Filters Three phase and neutral - general performance This three phase and neutral fi lter series provides a good level of attenuation across a broad frequency spectrum. The fi lter housing`s small footprint and ...

Page 4

Chassis Mount Filters - Motor Drive Filters Three phase and neutral - general purpose This three phase and neutral fi lter series provides a cost-effective level of suppression within a compact enclosure. The fi lter housing`s small footprint and low- ...

Page 5

Chassis Mount Filters - Motor Drive Filters ... 003AAW03 ... 010AAW01 ... 020AAW01 Insertion loss (typical): Asymmetrical (line to ground) ... 003AAW04 ... 006AAW04 ... 010AAW02 5 FLLD series AW type - - - Symmetrical (line to line) 11/2009 ...

Page 6

Chassis Mount Filters - Motor Drive Filters Three phase and neutral - high performance This family of three phase or three phase and neutral fi lters offer high attenuation across a broad frequency spectrum. The single or two stage designs ...

Page 7

Chassis Mount Filters - Motor Drive Filters FLLD series - BM ZS type 7 11/2009 ...