GT3A-1 IDEC Corporation, GT3A-1 Datasheet
![no-image](/images/no-image-200.jpg)
GT3A-1
Related parts for GT3A-1
GT3A-1 Summary of contents
Page 1
... AC/ T1: 0.1 sec to 300 hours 30V DC, 5A T2: 0.1 sec to 6 hours T1: 0.1 sec to 300 hours T2: 0.1 sec to 300 hours For details, see pages 1067 to 1072. Operating Voltage Type No. 100 to 240V AC GT3A-1AF20 100 to 240V AC GT3A-2AF20 24V AC/24V DC GT3A-2AD24 100 to 240V AC GT3A-3AF20 24V AC/24V DC GT3A-3AD24 100 to 240V AC ...
Page 2
... MΩ minimum (500V DC megger) Between power and output terminals: 2000V AC, 1 minute Between contacts of different poles: 2000V AC, 1 minute Between contacts of the same pole: 750V AC, 1 minute (GT3A-1, 2) 1000V AC, 1 minute (GT3A- Hz, amplitude 0.75 mm, 2 hours each in 3 directions 2 Operating extremes: 98 m/s ...
Page 3
... GT3 [Multi-Mode Type] Series Operation Chart Type No. GT3A-1 Contact Delayed SPDT Internal (~)/(+) Connection Operation Mode Selection 8 2 (~)/(-) On Delay T T Terminal erminal Item Operation No. No. MODE Set Time Power 2-7 A 5-8 (NC) Delayed Contact 6-8 (NO) POWER Set timer for desired delay, Indicator apply power to coil. Contacts ...
Page 4
... GT3 GT3A-4, -5, -6 Four Selectable Operation Modes with Start, Gate, and Reset Inputs for External Control Type List (1) Operation Mode A: ON Delay B: Cycle OFF C: Signal ON Delay D: Signal OFF Delay A: Interval ON B: One-Shot Cycle, C: Signal ON/OFF Delay D: Signal OFF Delay A: One-Shot B: One-Shot ON Delay ...
Page 5
... GT3 [Multi-Mode Type with Inputs (11 Pins)] Series Operation Chart • GT3A-4 Contact Internal Connection Operation Mode Selection On Delay Item Power MODE Start A Reset Gate Delayed Contact Power is applied to timer at all times. Set time for desired delay. When start input is supplied time delay starts, contacts transfer after preset time has elapsed ...
Page 6
... GT3 • GT3A-5 Contact Internal Connection Operation Mode Selection Interval ON Item Power MODE Start A Reset Gate Delayed Power is applied to timer at all times. Set Contact timer for desired delay, initiate start input. Contacts immediately transfer. After preset delay contacts return to original position. ...
Page 7
... GT3 [Multi-Mode Type with Inputs (11 Pins)] Series • GT3A-6 Contact Internal Connection Operation Mode Selection One Shot Item Power MODE Start A Reset Gate Delayed Contact Power is applied to timer at all times. Set timer for desired delay, initiate start input. Contacts immediately transfer. After ...
Page 8
GT3F-1/GT3F-2 Specifically designed type for Power OFF Delay. Reset Inputs are available. Type List (1) Operation Mode Rated Voltage Code 100 to 240V AC 24V AC/24V DC Power OFF Delay 100 to 240V AC 24V AC/24V DC Time Ranges • ...
Page 9
GT3 [Power OFF Delay Type] Series Operation Chart Contact Internal Connection GT3F-1 Delayed SPDT Output with Reset Input (~)/(+) Reset (~)/(-) GT3F-2 Delayed DPDT Output (~)/(+) ...
Page 10
GT3S-1/GT3S-2 Star-Delta Output Mode Type List (1) Operation Mode Rated Voltage Star-Delta 100 to 240V AC Time Ranges 2 Star-Delta Switching 1 Star Dial Selector Dial Time Range Indication 0.05 sec -- 5 sec 0. ...
Page 11
GT3 [Star-Delta Type] Series Operation Chart Contact Internal Connection GT3S-1 Star : Delayed SPST-NO Delta: Delayed SPST- GT3S-2 Star : Delayed SPST-NO Delta: Delayed SPST-NO Instantaneous SPST- 1076 Terminal Item No. ...
Page 12
GT3 GT3W-A11, -A13, -A31, A33 Multi-range Twin-Timer type with 8 operation modes Type List (1) Operation Mode Sequential Start Coarse/Fine Adjustment Instantaneous Cycle Cycle Cycle Inversion Interval ON Interval ON Delay Sequential Interval Time Ranges 0.1 sec to 6 hours ...
Page 13
GT3 Multi-function Timers [Twin-Timer Type] Series Operation Chart Operation Chart Delayed SPDT + Delayed SPDT Contact Operation Mode 1 8 Selection Sequential Start Terminal Item Operation No. Power 2-7 A 1-4 Delayed (NC) Contact 1-3 Ry1 ...
Page 14
Applicable Sockets & Hold-Down Springs (Optional) • DIN Rail Mount Socket Item 8-Pin Screw Terminal Socket 11-Pin Screw Terminal Hold-Down Spring Note: All are UL recognized, CSA certified, and TÜV approved. SR2P-06A SR3P-05A • Panel Mount Socket Item 8-Pin Solder ...
Page 15
... GT3 Multi-function Timers [All] Series Dimensions When Using DIN Rail Mount Socket (SR2P-06A Socket) • GT3A-1, -2, -3/GT3F/GT3S (8-pin) (When using DIN rail) BAA, BAP: 99 max. (Note 1) 95 max. (Note 2) Hold-Down Spring ( SFA-202 ) 36 8 64.2 13 Note 1: For SR2P-05A: 105.5 max. For SR2P-05C: 107 max. ...
Page 16
All GT3 Series When using DIN 48mm-square Panel Mount Adapter (For 8-pin solder wiring socket adapter: SR6P-S08 and 11-pin solder wiring socket adapter: SR6P-S11) (8-pin Screw Terminal Wiring Socket Adapter: SR6P-M08G) Panel Thickness: 0 (11-pin Screw ...
Page 17
... Since this selector does not turn infinitely, turn the selector clockwise when Mode A is displayed and counterclockwise when Mode D is displayed. Operation Mode Selector • Mode Code and Operation Mode Type No. GT3A-1, -2, -3 GT3A-4 MODE Code A ON Delay ON Delay Interval ON ...
Page 18
... Since DC types have a polarity in their power supply connection, 0.05 sec connect the power according to wiring diagram. 0.1 sec • Since AC type GT3A, GT3S, and GT3W comprise a capacitive 0.25 sec load, the SSR dielectric strength should be two or more times as 0.5 sec large as the power voltage when switching the timer power using an SSR. • ...
Page 19
... GT3 Series Timer Input Terminal Circuit Insulating Transformer • Do not connect input signal terminals of the GT3A timer to other terminals than No. 2. Never apply voltage to input signal terminals. Otherwise, the internal circuit may be damaged and 7 Input Terminal 2 10 • ...
Page 20
Temperature Error This indicates the influence caused by the change in temperature during operation within operating temperature. This is shown with the variance of operation time × 100 (%) = ± Tt: Average of ...