PROTECTION
Parameter
Thermal Shutdown
Input Protection
Over-voltage Protection
Parameter
Output Overload Protection
Hot-Swap Capability
Output Fault Isolation
GENERAL CHARACTERISTICS
Parameter
Efficiency
MTBF
Weight
STATUS & CONTROL SIGNALS & INDICATORS
Name
Enable (EN#)
Output Inhibit (INH#)
Output Fault (FAL#)
Remote Sense (RS+, RS-)
Thermal Warning (DEG#)
Fault Indicator LED
Power Present Indicator LED
ENVIRONMENTAL CHARACTERISTICS
Parameter
AmbientOperatingTemperature
Ambient Storage Temperature
Humidity
Altitude
Airflow
Description
Short pin (#27) on connector will enable the outputs when the mating pin is grounded. Supply will not power up until this pin is engaged to
its mate in the backplane. Unit output will be inhibited as pin is disengaged from the mating connector.
Secondary referenced; active low, TTL compatible. Logic “0” or short circuit to output return inhibits all outputs.
Secondary referenced. Open collector signal denotes that one of the output voltages has fallen below the lower regulation limit.
Connection of the sense leads across the load at the desired point of regulation will compensate for voltage distribution drops up to 500mV
between the output terminals of the power supply and the point of connection. The unit reverts to local sensing if the sense lines are opened
for any reason. The output is protected against shorted or open leads. Applies to outputs V1-V3.
Secondary referenced; TTL compatible. Open collector denotes a thermal warning; nominally, 10ºC prior to thermal shutdown.
An LED will illuminate red if the output voltages are not within specification, coincident with assertion of the FAL# signal.
A green LED will be illuminated when the input voltage is present and above the minimum requirement.
Conditions
De-rate output power linearly above 50ºC to 420W at 70ºC with 400lfm airflow. See the de-rating
chart on page 4 for additional data.
Operating; non-condensing
Storage; non-condensing
Operating. De-rate operating ambient temperature by 2Cº per 1000ft above 5000ft.
Storage
See de-rating chart on page 4 for additional data on cooling.
Conditions
48Vdc input, 420W load
Calculated per MIL-HDBK-217F, 25ºC ambient, ground benign
Calculated per MIL-HDBK-217F, 50ºC ambient, ground benign
Unpackaged
Conditions/Response
Automatic recovery upon restoration to operational temperatures
Internal line fuse, Littlefuse 314020 or equivalent (fast-acting 3AB)
All outputs
Conditions/Response
Outputs are individually protected against overloads and indefinite short circuit with automatic recovery upon removal of the
fault condition. Overload response for all outputs is hiccup mode.
Design Verification Testing (DVT) confirms that voltage excursions on the output buses resulting from insertion/extraction
events do not exceed the specified maximum of 8%. However, routing of power and signal lines in the mating backplane is
critical to minimization of such excursions. In addition, performance can be critically affected by load characteristics including
resistance, negative resistance, and reactive components. While the control loop responses have been designed for optimum
hot-swap performance over a wide range of characteristics, there may be instances where the voltage excursions exceed
published specifications. In such cases, the control loop responses can be modified to perform optimally.
Output isolation devices are present in all outputs to isolate faults within a failed power supply.
420W 6Ux8HP DC/DC CompactPCI™ Power Supply
cPCI420 Series
cPCI420 SERIES
-200
-200
400
Min
-20
10
0
5
110
Min
Min
374
174
RevA 02/2006
Typ
125
Typ
90
Typ
0.7
Inception
68
10000
50000
Max
145
Max
20
70
85
90
90
Max
Page 2 of 4
%Vnom
Units
Units
Units
ºC
khrs
khrs
A
lfm
Kg
ºC
ºC
%
%
%
ft