F4-08AD Automation Direct, F4-08AD Datasheet

no-image

F4-08AD

Manufacturer Part Number
F4-08AD
Description
Analog Input Modules
Manufacturer
Automation Direct
Datasheet
6–74
Number of Channels
Input Ranges
Channels Individually
Configurable
Resolution
Active Low-pass Filtering
Input Impedance
Absolute Maximum Ratings
Conversion Time
Linearity Error (End to End)
Input Stability
Full Scale Calibration Error
(Offset error not included)
Offset Calibration Error
Voltage Transmitter
Voltage Transmitter
3-wire 4-20mA
2-wire 4-20mA
Not used
Transmitter
Transmitter
CH3-6
CH2
CH1
PLC Products
CH7
CH7
F4-08AD 8-Channel Analog Input <--->
See Note 1
8, single ended (one common)
0-5V, 0-10V, 1-5V, ±5V, ±10V
0-20mA, 4-20mA
No. Each channel can be configured for current or
voltage but must be same range.
12 bit (1 to 4,096)
-3dB at 20Hz, -12 dB per octave
250 ± 0.1%, 1/2W current input
>20M voltage input
1 M minimum
-45mA to + 45mA, current input
-75V to +75V, voltage input
0.4ms per channel (module conversion)
1 ms per selected channel minimum (CPU)
± 1 count (0.025% of full scale) max.
± 1/2 count
± 12 counts voltage input
± 12 counts max. @ 20mA current input
± 2 counts max., unipolar voltage input
± 4 counts max., bipolar voltage input,
± 4 counts max., 4mA current input
PLC Update Rate
Digital Input Points Required
Base Power Required 5V
Terminal Type (included)
External Power Supply
Recommended Fuse
Operating Temperature
Accuracy vs. Temperature
Storage Temperature
Relative Humidity
Environmental Air
Vibration
Shock
Noise Immunity
One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
NOTE 1: Shields should be grounded at the signal source
NOTE 2: Unused channels should be connected to 0V or have current jumpers installed
More than one external power supply can be used (see channel 8)
A Series 217, 0.032A, fast-acting fuse is recommended for 4-20mA current loops.
If the power supply common of an external power supply is not connected to 0VDC on the module,
then the output of the external transmitter must be isolated. To avoid “ground loop” errors,
recommended 4-20mA transmitter types are:
2 or 3 wire:
4 wire:
Isolation between input signal and power supply.
Isolation between input signal, power supply and 4-20mA output.
1 channel per scan min., 8 per scan, max.
16 (X) input points (12 binary data bits, 3
active channel bits, 1 bit unused)
75mA
Removable (D4-16IOCON)
18-30VDC, 120mA, class 2
0.032 A, Series 217 fast-acting, current inputs
32° to 140°F (0 to 60°C)
± 50 ppm/°C maximum full scale (including
maximum offset change of 2 counts)
-4 to 158°F (-20 to 70°C)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
NEMA ICS3-304
1 - 8 0 0 - 6 3 3 - 0 4 0 5