INSTALLATION AND MAINTENANCE INSTRUCTIONS
EM-1RI Relay Module
SPECIFICATIONS
Normal Operating Voltage:
Standby Current:
Alarm Current:
Short Circuit Current, Dry Control Input:
Maximum Resistance, Dry Contact Input:
Temperature Range:
Humidity:
Dimensions:
Accessories:
NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC.
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the
appropriate control panel installation manual for detailed system information.
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
Relay Module, Model EM-1RI, is to be designed for use in activation of the
types of products that are generally connected to an intelligent fire alarm sys-
tem. It provides two sets of form C contacts that switch together (one DPDT
relay). There is also an input that is capable of monitoring a dry set of contacts
for open or closed conditions. The module also has on-board short circuit iso-
lators to prevent shorts on the signaling line circuit from disabling more than
one device on the intelligent loop.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a listed compat-
ible control panel.
MOUNTING
The module mounts directly to 4-inch square electrical boxes. The box must
have a minimum depth of 2
row facing upward for proper operation of the IR programming tool. Surface
mounted electrical boxes (SMB500) are available from System Sensor.
D500-61-00
CURRENT RATING
1.5 A
.9 A
.9 A
.5 A
.3 A
.7 A
3 A
2 A
1 A
2 A
LED INDICATOR
1
8
inches. Modules must be mounted with the ar-
15 to 30 VDC
580 µA max. average (continuous broadcasts)
2.0 mA (red LED on)
30 µA max. average (5VDC)
100 Ω
32°F to 120°F (0°C to 49°C)
10% to 93% RH Non-condensing
4.17˝ H × 4.26˝ W × 1.22˝ D; (106 mm H × 108 mm W × 31 mm D)
Wall cover plate (included); SMB500 Surface Mount Electrical Box; CB500 Control Module Barrier
MAXIMUM VOLTAGE
IR RECEIVER
70.7 VAC
110 VDC
125 VDC
125 VAC
30 VDC
30 VDC
30 VDC
30 VDC
25 VAC
25 VAC
C0166-00
1
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances,
and regulations.
1.
2.
3.
AUTO ADDRESSING
Eclipse Series devices are capable of supporting auto addressing, if the fire
alarm control panel is designed to do so. In auto addressing, the control panel,
through the use of each device’s on-board isolators, can automatically assign
device addresses.
In order to control which devices are addressed first in wiring configurations
with branches, a branch marker can be set at a particular device. A branch
marker is an electronic value from 0 to 255 stored in the device memory. The
branch markers are set with the IR configuration tool, EA-CT.
TERMINAL DEFINITIONS
All relay switch contacts are shipped in the standby state (open) state, but may
have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to com-
municate with the panel before connecting circuits controlled by the module.
T1
T2
T3
T4
T5
T6
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
NOTE: Separate cable entry openings must be used to maintain required
spacing between power limited and non-power limited wiring. Optional
EA-CB may be required to separate power limited and non power limited
wiring in the electrical box.
Set the address on the module per job drawings using the IR configura-
tion tool (model no. EA-CT).
Secure module to electrical box (supplied by installer).
LOAD DESCRIPTION
Inductive (L/R=5ms)
Inductive (L/R=2ms)
Inductive (PF = .35)
Inductive (PF=.35)
Inductive (PF=.35)
Inductive (PF=.35)
(+) SLC in/out
(–) SLC in/out
(+) SLC in/out
(–) SLC in/out
(+) Dry Contact Input
(–) Dry Contact Input
Resistive
Resistive
Resistive
Resistive
3825 Ohio Avenue, St. Charles, Illinois 60174
WARNING
T10
T11
T12
T7
T8
T9
1.800.SENSOR2; Fax: 630.377.6495
Normally Closed #1
Common #1
Normally Open #1
Normally Closed #2
Common #2
Normally Open #2
APPLICATION
Non-Coded
Non-Coded
Non-Coded
Non-Coded
Non-Coded
Non-Coded
Non-Coded
www.systemsensor.com
Coded
Coded
Coded
I56-2023-005

Related parts for EM-1RI

EM-1RI Summary of contents

Page 1

... NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION Relay Module, Model EM-1RI designed for use in activation of the types of products that are generally connected to an intelligent fire alarm sys- tem. It provides two sets of form C contacts that switch together (one DPDT relay) ...

Page 2

... Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the module which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’ ...