dla71db Carlo Gavazzi Inc., dla71db Datasheet - Page 2

no-image

dla71db

Manufacturer Part Number
dla71db
Description
Monitoring Relays Pump Alternating Type Dla71
Manufacturer
Carlo Gavazzi Inc.
Datasheet
General Specifications
DLA71
Supply Specifications
Power supply
Dielectric voltage
Rated operational power
Reaction time
Continous working time to
activate the rotation pumps
Mode of Operation
DLA71 is made for pumping
systems where 2 or 3 pumps
are in parallel. It lets the
pumps work alternatively,
allowing more pumps to
work togheter in case of
need.
Example 1
(emptying a basin, 2-pump
system)
As soon as the liquid reach-
es switch S1 one pump
starts.
switches back the pump
stops. When switch S1 is
activated again the other
pump starts allowing uni-
form wear and tear of all the
pumps. If switch S2 is acti-
vated both pumps start (2
pumps running at the same
time). When S2 switches
back
since most time stops.
2
Rated operational voltage
through terminals:
Supply to input
Supply to output
Input to output
AC
A1, A2 or A3, A2
Minimum delay to activate
the
As
the rescue pumps
pump
soon
Opening input
Closing input
as
running
B48:
B23:
S1
Overvoltage cat. III
(IEC 60664, IEC 60038)
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
4 kV (1.2/50 µs)
4 kV (1.2/50 µs)
4 kV (1.2/50 µs)
3 VA
< 100 ms
< 100 ms
10 s
6 h ± 10%
Example 2
(emptying a basin, 2-pump
system, differential mode)
In this case the pumps are
separately
stopped by the two pairs of
switches S1, S2 and S3, S4.
Appropriate
allows the pumps to work
together in case of need.
Note (2-pump system)
If the system is continuously
working with only one pump,
after working for 6 hours,
DLA71 stops the pump and
the second one automatical-
ly starts.
This rotation is repeated
every 6 hours of single and
continuative
pump.
Example 3
(emptying a basin, 3-pump
system, normal mode)
The system works exactly as
described
except that if switch S3 is
in
started
work
example
positioning
of
and
1
a
General Specifications
reached three pumps work
at the same time. When they
switch back the pumps are
turned off in sequence start-
ing from the one running
longer.
Example 4
(emptying a basin, 3-pump
system, full mode)
As soon as the liquid reach-
es switch S1 one pump
starts. When it drops below
switch S4 it stops. If switch
S1 is triggered again another
pump starts. If switch S2 is
activated a second pump
starts (rescue function). If
switch S3 is activated all the
pumps operate. The only
switch to stop all the pumps
active at a certain time is S4.
Note (3-pump system)
If the system is continuously
working with only one pump,
after working for 6 hours,
DLA71 stops the pump and
the second one automatical-
Indication for
First pump activated after
power up
Environment
Housing
Weight
Screw terminals
Approvals
CE Marking
EMC
Power supply ON
One Pump ON
Two Pumps ON
Three Pumps ON(DLA71...3P) as above, flashing 3 Hz
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Dimensions
Material
Tightening torque
Immunity
Emission
Specifications are subject to change without notice (25.06.07)
ly starts. If also the second
pump works continuously
alone for 6 hours, it is
stopped and the third pump
is then started.
If a couple of pumps is con-
tinuously
hours, the one running for
more time stops and the free
one starts.
This rotation is repeated
every 6 hours of continuative
work of a pump or a couple
of pumps.
Note (2 and 3-pump sys-
tems)
In case the task is to fill a
basin, all the switches are
reversed in the basin itself.
LED, green, steady
as above, flashing 1 Hz
as above, flashing 2 Hz
Note: if more than one pump
is active, the indication refers
to the pump started last.
Random
(EN 60529)
IP 20
3
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
35.5 x 81 x 67.2 mm
PA 66
Approx. 135 g
Max. 0.5 Nm
acc. to IEC 60947
UL, CSA
Yes
Electromagnetic Compatibillity
According to EN 61000-6-2
According to EN 61000-6-3
working
for
6