k3hb-s Omron Corporation, k3hb-s Datasheet
k3hb-s
Related parts for k3hb-s
k3hb-s Summary of contents
Page 1
... Accessories (Sold Separately) K32-DICN: Special Cable (for event inputs, with 8-pin connector) K32-BCD: Special BCD Output Cable CSM_K3HB-S_DS_E_4_1 Base Units with Optional Boards K3HB-S@-@@@ Sensor Power Supply/Output Type Code None: None CPA: Relay output (PASS: SPDT) + Sensor power supply (12 VDC +/− ...
Page 2
... DC power supply models. The OMRON S8VS-series DC Power Supply Unit is recommend- ed. 2. PNP input types are also available. 3. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for Thin Cables. 24 VAC/VDC, DeviceNet power supply: 24 VDC DeviceNet power supply VDC Load: 500 Ω ...
Page 3
... Indication range −2.000 to 22.000 mA 120 Ω max. 2.000 to 22.000 mA −0.500 to 5.500 mA 1 MΩ min. 0.500 to 5.500 V ±5.500 V ±11.000 V K3HB-S Input Accuracy Maximum impedance (at 23±5°C) absolute rated input One input: ±31 mA ± ...
Page 4
... The range shown in dark shading indicates the factory setting. Sampling and Comparative Output Response Times The K3HB-S sampling and comparative output response times depend on the calculation methods, timing hold type, and, for simple averaging, the averaging times. Refer to the following description for details. ...
Page 5
... OVER DATA VALID RUN HH H PASS L LL Note: For details on serial and DeviceNet communications, refer to the Digital Indicator K3HB Communications User's Manual (Cat.No. N129). K3HB-S TIMING 24 VDC 50 mA 100 µA max Item Rating Input signal No-voltage contact input ...
Page 6
... Transistor circuit output Micro- computer Drive Relay output X circuit Drive DeviceNet DeviceNet circuit circuit Communi- Drive cations Communications circuit driver COM V O DC-DC Converter (isolated) K3HB-S Drop line length Total drop line (max.) length (max 156 m 6 ...
Page 7
... UP MODE Key Used to switch the Used to change parameters displayed. parameter settings. When changing a set value, this key is used to move along the digits. K3HB display Displays PVs, maximum values, minimum values, parameter names, and error names. Position meter Displays the position of the PV with respect to a desired scale ...
Page 8
... V Refer to the following User's Manual for application precautions and other information required when using the Digital Indicator: K3HB-S/-X/-V/-H Digital Indicator User's Manual (Cat. No. N128) The manual can be downloaded from the following site in PDF format: OMRON Industrial Web http://www.fa.omron.co.jp Continuous Data Output REQ ...
Page 9
... K3HB-S 9 ...
Page 10
... DeviceNet power supply. • The product must be used indoors for the above applicable standards to apply. • The K3HB-XVA@@ complies with UL standards when the applied input voltage is within the range 0 to 150 VAC. K3HB DeviceNet Connector (Included) < ...
Page 11
... DDK) Wiring Pin No. Signal name 1 N/C 2 S-TMR 3 HOLD 4 RESET 5 N/C 6 COM 7 BANK4 8 BANK2 9 BANK1 10 COM K3HB-S Linear Sensor Indicator K3HB-H K3HB Input B Current input E2 E2 N/C Input COM Voltage input Input Input COM E6 ...
Page 12
... Previous Average Value Comparison Slight changes can be removed from input signals to detect only extreme changes. Input value 2 Input value 1 Input value (inp.a2) (inp.a1) (Reverse scaling) K3HB-S K−A Sampling hold value ON Peak-to-peak value (b2−a2) (b1−a1) b1 'b2 a1 ...
Page 13
... For example, if the setting is 2, the small- est digit will only take the values and if the setting will only take the values the setting is 10, it will only take the value of 0. Input Red 110 110 K3HB-S 13 ...
Page 14
... PASS output terminal. Terminal cover (included) 91 Character Size for Main Display (mm) PV display SV display 14.2 100 (112) 7.6 12 1.3 95 *DeviceNet models Terminal: M3, Terminal Cover: Accessory K3HB-S Hysteresis Hysteresis Input Startup H output compensation time set time H input Panel Cutout Dimensions 120 min. 4.9 3.5 75 min. +0 ...
Page 15
... If the rubber packing is lost or damaged, it can be ordered using the following model number: K32-P1. (Depending on the operating environment, deterioration, contraction, or hardening of the rubber packing may occur and so, in order to ensure the level of waterproofing specified in NEMA4, periodic replacement is recommended.) Note: Rubber packing is provided with the Controller. K3HB-S 15 ...
Page 16
... OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ Read and Understand This Catalog Warranty and Limitations of Liability Application Considerations Disclaimers In the interest of product improvement, specifications are subject to change without notice. (c)Copyright OMRON Corporation 2008 All Right Reserved. 2008.11 ...