PLS_GEN (Pulse generator)
(Write Real type parameter)
(Write Integer type parameter)
(Standard PID operation)
(Cascade PID operation)
PAW_REAL
MAN
RUN
LOCAL
M_SP
M_PV
S_LSP
S_PV
RSP_H
RSP_L
M_PID
S_PID
PARA
MONI
AT
MV_IN
RUN
CYCLE
TYP
ID
NO
W_VAL
paw_real
TYP
ID
NO
W_VAL
MODE
SP
PV
PID
PARA
MONI
AT
MV_IN
pls _ gen
paw_int
pid_cas
PAW_INT
PID_CAS
pid_a
PID_A
AT_MD
S_RSP
E_OK
E_OK
E_OK
E _ OK
E_OK
OUT
MV
MV
Input parameter
Output parameter
Description
Input parameter
Output parameter
Description
Input parameter
Output parameter
Description
Input parameter
Output parameter
Description
Input parameter
Output parameter
Description
TYPE: Integer type, Parameter type ID
ID: Integer type, Group ID
NO: Integer type, Item ID
W_VAL: Integer type, data to be written
E_OK: Boolean type, TRUE=Normal, FALSE=Error
Integer type data is written into a DMC50’s dedicated parameter.
TYPE: Integer type, Parameter type ID
ID: Integer type, Group ID
NO: Integer type, Item ID
W_VAL: Real type, data to be written
E_OK: Boolean type, TRUE=Normal, FALSE=Error
The real type data is written into a DMC50’s dedicated parameter.
MODE: Boolean type, TRUE=MANUAL mode, FALSE=AUTO mode
SP: Real type, SP (industrial unit)
PV: Real type, PV (industrial unit)
PID: Integer type, Designates the group ID of PID_A constants
PARA: Integer type, Designates the group ID of PID_A options
MONI: Integer type, Designates the group ID of PID_A monitor
AT: Boolean type, Start/stop of auto-tuning
MV_IN: Real type, Outputting value at MANUAL mode
E_OK: Boolean type, TRUE=Normal, FALSE=Error
MV: Real type, Manipulated variable
A series form PID operation of which derivative action applied on error
MAN: Boolean type, TRUE=MANUAL mode, FALSE=AUTO mode
RUN: Boolean type, TRUE=RUN mode, FALSE=READY mode
LOCAL: Boolean type, TRUE=LOCAL mode, FALSE=REMOTE mode
M_SP: Real type, Master side SP (industrial unit)
M_PV: Real type, Master side PV (industrial unit)
S_LSP: Real type, Slave side LSP (industrial unit), For LOCAL mode
S_PV: Real type, Slave side PV (industrial unit)
RSP_H: Real type, RSP scale upper limit (industrial unit)
RSP_L: Real type, RSP scale lower limit (industrial unit)
M_PID: Integer type, Designation of group ID for PID_CAS constants (master side)
S_PID: Integer type, Designation of group ID for PID_CAS constants (slave side)
PARA: Integer type, Designation of group ID for PID_CAS options
MONI: Integer type, Designation of group ID for PID_CAS monitor
AT: Boolean type, Start/stop of auto-tuning
MV_IN: Real type, Outputting value at MANUAL mode
E_OK: Boolean type, TRUE=Normal, FALSE=Error
AT_MD: Boolean type, TRUE=During AT, FALSE=AT stop
S_RSP: Real type, Slave side remote SP (industrial unit)
MV: Real type, Manipulated variable
PID operation for cascade control
RUN: Boolean type, TRUE=Execution, FALSE=Reset
CYCLE: Timer type, CYCLE≥Cycle time setting
E_OK: Boolean type, TRUE=Normal, FALSE=Error
OUT: Boolean type, Pulse output
A one cycle time pulse is generated at each designated cycle.
29