P48-55-00 SYSTEMSENSOR [Systemsensor advanced ideas.], P48-55-00 Datasheet - Page 2

no-image

P48-55-00

Manufacturer Part Number
P48-55-00
Description
4-Wire Ionization Duct Smoke Detector
Manufacturer
SYSTEMSENSOR [Systemsensor advanced ideas.]
Datasheet
Innovair Duct Smoke Detector Specifications
A05-0315-002
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor Model DH100ACDCI Series Duct Smoke Detector. The detector housing shall be UL listed per UL 268A
specifically for use in air handling systems. The detector shall operate at air velocities of 500 feet per minute to 4000 feet per minute (2.54 to 20.32 meters/
second). The unit shall be capable of controlling up to ten (10) air handling systems when interconnected with other detectors. The detector shall be capable of
providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch or remote testing using the SSK451
Multi-Signaling Accessory or the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or remote test station. The duct smoke detector
housing shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The housing shall be
capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall be included to reduce dust and residue effects
on detector and housing, thereby reducing maintenance and servicing. Sampling tubes shall either be telescoping or be easily installed by passing through the
duct housing after the housing is mounted to the duct. The unit shall provide a spacial separation of no less than ¼˝ (6.4 mm) and/or a physical barrier between
the high and low voltage terminals. The enclosure shall meet all applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections
shall be of the strip and clamp method suitable for 12–18 AWG wiring.
Physical Specifications
Size
Shipping Weight
Operating Temperature Range
Operating Humidity Range
Air Duct Velocity
Electrical Ratings – DH100ACDCLP (Includes Detector)
Power supply voltage:
Input capacitance:
Reset voltage:
Reset time (with RTS451):
Reset time (by power down):
Power up time:
Alarm response time:
Sensitivity Test:
Current Requirements (Using No Accessories)
Max. standby current:
Max. alarm current:
Contact Ratings
Alarm initiation contacts (SPST):
Alarm auxiliary contacts (DPDT):
Note: Alarm auxiliary contacts must switch 100mA minimum at 5 VDC. Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use
Trouble contacts (SPDT):
Accessory Current Loads at 24 VDC
Device
APA451
PA400
RA400Z
RTS451/RTS451KEY
SSK451
*Note: When a unit is powered at the 120 VAC or 220/240 VAC input, any combination of accessories may be used such that the given accessory loads are: 60
the alarm initiation contact for this purpose.
mA or less in the standby state; 110 mA or less in the alarm state.
20-29 VDC
270 µF max.
3.0 VDC min.
.03 to 0.3 sec.
0.6 sec. max.
34 sec. max.
2 to 17 sec.
See detector label
15 mA
70 mA
2.0A @ 30 VAC/DC (0.6 power factor)
10A @ 30 VDC; 10A @ 250 VAC
2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive)
Standby
12.5 mA Max.
0 mA
0 mA
12 mA*
5 mA Max.
143⁄8˝ (37 cm.) Length; 5½˝ (14 cm.) Width; 2¾˝ (7 cm.) Depth
3¾ lbs. (1.7 kg.)
32° to 120°F (0° to 49°C)
10% to 93% relative humidity non-condensing
500 to 4000 ft./min. (2.54 to 20.32 m/sec.)
24 VAC 50-60 Hz
.03 to 0.3 sec.
0.6 sec. max.
34 sec. max.
2 to 17 sec.
See detector label
35 mA RMS
125 mA RMS
Trouble
n/a
n/a
n/a
n/a
9 mA Max.
270 µF max.
2.0 VAC min.
120 VAC 50-60 Hz
N/A
10 VAC min.
.03 to 0.3 sec.
0.6 sec. max.
34 sec. max.
2 to 17 sec.
See detector label
25 mA RMS
35 mA RMS*
Alarm
30 mA Max.
15 mA Max.
10 mA Max.
7.5 mA Max.
30 mA Max.
220/240 VAC 50-60 Hz
N/A
.03 to 0.3 sec.
34 sec. max.
2 to 17 sec.
See detector label
15 mA RMS*
25 mA RMS*
20 VAC min.
0.6 sec. max.