DP-FLEX GAMEWELL-FCI [Gamewell-FCI by Honeywell], DP-FLEX Datasheet

no-image

DP-FLEX

Manufacturer Part Number
DP-FLEX
Description
Two-Zone Fire Alarm Control Panel
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Flex 402
Two-Zone Fire Alarm Control Panel
cludes the ability, using a single pair of wires, to silence audible devices while
strobes continue to flash.
The Flex 402 is also compatible with conventional input devices such as two-
and four-wire smoke detectors, pull stations, waterflow devices, tamper switches
and other normally-open contact devices.
Operation
The activation of a compatible smoke detector or any normally-open fire alarm
initiating device will: activate audible and visual signaling devices, illuminate an
indicating LED, sound the piezo sounder at the FACP, activate the FACP alarm
relay, and operate an optional module which notifies a remote station or initiates
an auxiliary control function.
i³ ™ Technology Features
• Drift compensation automatically adjusts detector sensitivity and increases
• The maintenance alert LEDs (per zone) warn of excessive dirt accumulation,
• Detector sensitivity is automatically measured. The twice-yearly test require-
• The wireless handheld sensitivity meter eliminates the need for voltmeters,
• The supervisory LED (per zone) provides a warning if a detector senses tem-
• Special test protocol and LED indication allow a quick test of all detectors —
• Electronic heat-sensing element provides thermal detection in addition to pho-
Flex 402 Two-Zone FACP CS-2402 09/01/06
resistance to false alarms caused by dust accumulation.
preventing false alarms.
ments of NFPA 72 (7-3.2.1) are met without using a ladder or test meter.
magnets, or a physical connection to the detector. The reader displays sensi-
tivity in terms of percent-per-foot obscuration and provides text status indica-
tion.
peratures approaching freezing.
without a ladder.
toelectronic smoke detection.
provides advanced features including
drift compensation, maintenance alert,
and freeze warning. Automatic synchro-
nization of audio/visual devices is pro-
vided, selectable for three manufactur-
ers’ protocols. The NAC protocol in-
Description
The Gamewell Flex 402 Fire Alarm
Control Panel brings the latest in mi-
croprocessor technology to conven-
tional fire controls. The Flex 402 is
compatible with the new i³ ™ smoke
detectors from System Sensor, and
Page 1 of 2
Features
• Two Style B (Class B) Initiating Device
• One Style Y (Class B) Notification Appliance
• 24 VDC.
• NAC synchronization features:
• Silent or Audible Walk Test operation mode
• Alarm verification selectable per zone.
• Each zone may be programmed for
• Disable switches provided for each zone.
• NACs programmable for: Silence Inhibit, Auto
• Form-C Alarm and Trouble relays.
• 3.0 amps total usable current.
• Optional dress panel (P/N DP-FLEX).
• Piezo sounder for alarm, trouble, supervisory,
• Control buttons: ACK (Acknowledge), Alarm
• LED indicators: Fire Alarm (one per zone),
Listings
• UL Listed: file S521.
• CSFM approved: file 7165-1288-180.
• MEA approved: file 366-04-E.
Circuits (IDCs).
Circuit (NAC).
– Provides synchronization of standard ANSI
– Provides synchronization of ADA compliant
– Selectable for System Sensor, Wheelock,
– Selective Silence feature allows manual
commanded from the front keypad, with
automatic return to normal after one hour of
inactivity.
supervisory or fire; each zone has separate
red and yellow LEDs.
Silence, Strobe Synchronization, Selective
Silence (horn/strobe mute), Temporal or
Steady signal, Silenceable or
Nonsilenceable.
and maintenance.
Silence, Reset, Walktest,
Zone Enable/Disable (one per zone).
Supervisory (one per zone), Trouble (one
per zone), Maintenance (one per zone),
AC Power, NAC Disable, Zone Disable,
NAC Fault, System Trouble, Power Trouble,
Walktest, Alarm Silence, Earth Fault (on
circuit board), Battery Fault (on circuit board),
Charger Fault (on circuit board).
Listings and approvals below apply to the
basic Flex 402 panel. In some cases, certain
modules may not be listed by certain
approval agencies, or listing may be in
process. Consult factory for latest listing
status.
audible signals as required by NFPA 72
(3-8.4.1.2.3).
strobes per NFPA 72 (4-4.4.1).
and Gentex protocols.
silencing of horns while strobes continue to
flash on the same NAC.

Related parts for DP-FLEX

DP-FLEX Summary of contents

Page 1

... Silence (horn/strobe mute), Temporal or Steady signal, Silenceable or Nonsilenceable. • Form-C Alarm and Trouble relays. • 3.0 amps total usable current. • Optional dress panel (P/N DP-FLEX). • Piezo sounder for alarm, trouble, supervisory, and maintenance. • Control buttons: ACK (Acknowledge), Alarm Silence, Reset, Walktest, Zone Enable/Disable (one per zone). • ...

Page 2

... Ordering Information F402 Two-zone conventional FACP. BB-17F Battery box, required to house two batteries greater than 7 AH maximum of 18 AH. DP-FLEX Dress panel. TR-1-R Trim ring for semi-flush mounting. 52194 Flex 402 Installation and Maintenance Manual. i³™ trademark and Gamewell® registered trademark of Honeywell International Inc. ...