E5CS-Q1KJX OMRON [Omron Electronics LLC], E5CS-Q1KJX Datasheet - Page 4

no-image

E5CS-Q1KJX

Manufacturer Part Number
E5CS-Q1KJX
Description
Temperature Controller DIN-sized (48��48 mm) Temperature Controller Features Automatic P (proportional action) Tuning Function
Manufacturer
OMRON [Omron Electronics LLC]
Datasheet
E5CS-X
Specifications
Note: Set values must be within the allowable range limits for alarm values, control outputs, etc. If a set value does not satisfy the following
4
Supply voltage
Operating voltage range
Power consumption
Control output
Co
Alarm output
Setting accuracy
Indication accuracy
Hysteresis
Proportional band
Reset time
Rate time
Alarm output setting range
Alarm output setting range
(Absolute-value alarm mode)
Proportional period
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Humidity
Degree of protection
Life expectancy
Weight
Ratings
Characteristics
o ou pu
condition, select another range:
Minimum of temperature range x T
where:
T
X=Alarm value.
set
=Set temperature, and
Relay
Voltage
Set value coincides with indicated value, since no relative error exists between these values.
0.2% of full scale (during ON/OFF control)
3% to 20% (automatically adjusted according to the rise time of the controlled system)
4 minutes (fixed)
0.4 minutes (fixed)
0 to full scale for all modes except the absolute-value alarm mode (see note)
Same as switch-selectable standard temperature ranges shown at the top of the tables in
Ordering Information
2/20 seconds
500 ms (Output change period: 2 seconds; Indication change period: 2 seconds)
20 M min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 minute (between current-carrying terminals of different polarity)
Malfunction: 2 to 55 Hz, 2 G for 10 minutes each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75 mm double amplitude for 2 hours each in X, Y, and Z directions
Malfunction: 100 m/s
Destruction: 300 m/s
Operating: –10 to 55 C
Storage: –25 to 65 C
35% to 85% RH
IEC 144
Front panel: IP50
Rear panel: IP30
Terminals: IP00
Mechanical: 10,000,000 operations min. (relay output)
Electrical: 100,000 operations min. (relay output)
Approx. 170 g (main enclosure only)
0.5% of full scale, 1 digit max.
set
X x Maximum of temperature range
100 to 240 VAC 50/60 Hz
85 to 110% of rated supply voltage
Approx. 7 VA
3 A 250 VAC (resistive load), SPDT
20 mA 12 VDC, w/short-circuit protection circuit
1 A 250 VAC (resistive load), SPST-NO
2
2
, in 6 directions, 3 times each
, in 6 directions, 3 times each
E5CS-X

Related parts for E5CS-Q1KJX