20141-01 Tyco Electronics, 20141-01 Datasheet - Page 8

no-image

20141-01

Manufacturer Part Number
20141-01
Description
2/0
Manufacturer
Tyco Electronics
Datasheet
8
Use to Select Proper Size Terminal
The chart shows sizes and dimensions of various studs and the corresponding terminal stud hole sizes used with AMP devices.
For example, with stud #5 (.125 [3.18] Diameter), use AMP terminal device listed for #5 stud (.132 [3.35] Hole Diameter).
Terminal stud hole sizes may easily be checked by fitting sample terminal to black circle.
Wire Size Range
AWG 8 to 500 MCM
Test Sequences
Test Group 1
Mechanical Sequence
1. Secureness
2. Pullout
Test Group 2
Mechanical Sequence
1. Secureness
2. Static Heat
3. Pullout
U.S. Cust.
5/16"
1/4"
3/8"
0#6
0#8
#10
#12
#14
Stud Size
Metric
M3.5
M4
M6
M8
Stud Dia.
.138
3.51
.164
4.17
.190
4.83
.216
5.49
.242
6.15
.250
6.35
.312
7.92
.375
9.53
Dimensions are in inches and
millimeters unless otherwise
specified. Values in brackets
are metric equivalents.
Heavy Duty Seamless Terminals & Splices
Stud Size Chart
Description of UL 486A Test Procedures and Requirements for Terminals
Pullout Test Requirements
Terminal must not be separate from wire when
subjected to the listed load for one minute.
Note: Testing conducted on non-plated
copper wire with UL approved insulation.
Stud Hole Diameter
Wire Size
Typical Terminal
AWG
250
300
350
400
500
1/0
2/0
3/0
4/0
10.29
8
6
4
2
.147
3.73
.173
4.39
.212
5.38
.225
5.72
.252
6.40
.275
6.99
.336
8.53
.405
.005
0.13
.005
0.13
.005
0.13
.005
0.13
.005
0.13
.005
0.13
.005
0.13
.005
0.13
Dimensions are shown for
reference purposes only.
Specifications subject to change.
Force (lbs.)
Pullout
100
140
180
250
300
350
450
500
550
600
650
800
90
U.S. Cust. Metric
7/16"
1/2"
5/8"
3/4"
Stud Size
M12
M16
Technical Support
USA: 1-800-522-6752
Canada: 1-905-475-6222
Mexico: 01-800-733-8926
Stud Dia.
11.10
12.70
15.88
19.05
.437
.500
.625
.750
Static Heat Test Requirements
Requirement — Connector temperatures must
not exceed the ambient temperature plus 50°C
[90°F] after stability is attained.
Stability — A test sample is considered to have
attained a stable temperature when three readings
taken at not less than 10 minute intervals show no
more than a 2°C [3.6°F] variation between any two
readings.
Wire Size
AWG
250
300
350
400
500
1/0
2/0
3/0
4/0
6
4
2
www.tycoelectronics.com
Stud Hole Diameter
Typical Terminal
Catalog 1308674
11.76
13.34
16.38
19.81
.463
.525
.645
.780
Test Current
(Amperes)
Issued 4-02
125
170
230
265
310
360
405
445
505
545
620
.005
.005
.005
.005
95
0.13
0.13
0.13
0.13

Related parts for 20141-01