All EN_OUTs are deasserted if an overvoltage or under-
voltage fault is detected during power-up/power-down
(regardless of the critical fault enable bits). Under these
conditions, information of the failing slot is stored in
EEPROM r00h[3:0] unless r47h[1:0] is set to ‘11’ (see
Table 23).
If there is a tracking fault on a channel configured for
closed-loop tracking, a fault log operation occurs and
the bits representing the failed tracking channels are
set to ‘0’ unless r47h[1:0] is set to ‘11’ (see Table 24).
For critical faults, the MAX16046/MAX16048 can be
configured for one of two fault management methods:
autoretry or latch-on-fault. Set r4Fh[3] to ‘0’ to select
autoretry mode. In this configuration, the device will
shut down after a critical fault event and then restart fol-
lowing a configurable delay. Use r4Fh[2:0] to select an
autoretry delay from 20µs to 1.6s. See Table 25 for
more information on setting the autoretry delay.
Table 25. Fault Recovery Configuration
System Managers with Nonvolatile Fault Registers
REGISTER/
ADDRESS
EEPROM
4Fh
12-Channel/8-Channel EEPROM-Programmable
BIT RANGE
[2:0]
[5:4]
[7:6]
Power-Up/Power-Down Faults
[3]
Autoretry/Latch Mode
Autoretry Delay
000 = 20µs
001 = 12.5ms
010 = 25ms
011 = 50ms
100 = 100ms
101 = 200ms
110 = 400ms
111 = 1.6s
Fault Recovery Mode
0 = Autoretry procedure is performed following a fault event
1 = Latchoff on fault
Slew Rate
00 = 800V/s
01 = 400V/s
10 = 200V/s
11 = 100V/s
Fault Deglitch
00 = 2 conversions
01 = 4 conversions
10 = 8 conversions
11 = 16 conversions
Set r4Fh[3] to ‘1’ to select the latch-on-fault mode. In
this configuration EN_OUT_s are deasserted after a
critical fault event. The device does not re-initiate the
power-up sequence until EN is toggled or the Software
Enable bit is reset to ‘0.’ See the Enable section for
more information on setting the Software Enable bit.
If fault information is stored in EEPROM (see the Critical
Faults section) and autoretry mode is selected, set an
autoretry delay greater than the time required for the
storing operation. If fault information is stored in
EEPROM and latch-on-fault mode is chosen, toggle EN
or reset the Software Enable bit only after the comple-
tion of the storing operation. If saving information about
the failed lines only, ensure a delay of at least 60ms
before the restart procedure. Otherwise, ensure a mini-
mum 204ms timeout. This ensures that ADC conver-
sions are completed and values are stored correctly in
EEPROM. See Table 26 for more information about
required fault log operation periods.