AC Linesr
Datasheet

Specifications of IBAR12-20T

Rohs Status
Not applicable
Power - Max
2400W
Energy
1200J
Ac Outlets
12
Voltage - Input
120VAC
Features
Rack Mount
Cord Length
15' (4.57m)
Size
4.00" L x 17.50" W x 1.75" H (101.6mm x 444.5mm x 44.5mm)
Ac Input Connector
NEMA 5-15P
Connector - Ac Output
NEMA 5-15R
Weight
5.4 lbs (2.4kg)
Ac Output Connector
NEMA 5-15R
Media Lines Protected
-
Other names
TL261
Specifications
OVERVIEW
Intended Application
OUTPUT
Frequency compatibility
Output watts
Output volt amp
capacity (amps)
Outlet quantity / type
INPUT
Recommended
Electrical Service
Input connection type
Input plug features
Input cord length (ft.)
Voltage compatibility
(VAC)
LEDS ALARMS & SWITCHES
Switches
Diagnostic LEDs
Locking switch cover
SURGE / NOISE SUPPRESSION
AC suppression joule
rating
AC suppression
response time
Protection modes
Clamping voltage (RMS)
AC suppression surge
current rating
AC suppression
components used
Safe thermal fusing
UL1499 let through
rating
EMI / RFI filtering
Diagnostic LEDs confirm proper wiring and suppressor operation
Front panel switch controls power to all outlets
20 amp electrical capacity with circuit breaker
120VAC, 50/60Hz electrical compatibility
$25,000
Lifetime product warranty
Ultimate Lifetime Insurance
Computer Networks
50 / 60 Hz
2400
20
12(2 front NEMA 5-15R / 10 rear 5-20R)
120V (110-125V)
NEMA L5-20P locking input plug
Space-saving right angle input plug
15
120
Red illuminated power switch controls power to all outlets
PROTECTION PRESENT (green), LINE FAULT (red) and LINE OK (green)
Transparent locking switch cover prevents accidental shutoff
3840
NM = 0 ns. CM =
Includes full normal mode (H-N) and common mode (N-G / H-G) line surge suppression
140
96,000 amps
Metal oxide varistors, toroidal balanced chokes and VHF capacitors
Prevents unsafe conditions during extreme extended over-voltages and catastrophic occurrences
330V - UL Verified
40-80 dB
(USA, Canada & Puerto Rico only)