SU3000RTXL3UHV Tripp Lite, SU3000RTXL3UHV Datasheet

UPS 3KVA 2400W 8OUT RACK MOUNT

SU3000RTXL3UHV

Manufacturer Part Number
SU3000RTXL3UHV
Description
UPS 3KVA 2400W 8OUT RACK MOUNT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
Power Supply Regulatorr
Datasheet

Specifications of SU3000RTXL3UHV

Power - Rated
3kVA / 2400W
Ac Outlets
8 (UPS)
Features
DB9 Communications, SNMP Card Slot
Backup Time - Max Load
6 minutes
Voltage - Output Per Connector
208V (200, 208, 230, 220, 240V)
Voltage - Input
200 ~ 240V / 15A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA L6-20P
Connector - Ac Output
6 NEMA 6-15/20R and 2 NEMA L6-20R
Size
19.80" L x 17.30" W x 5.20" H (502.9mm x 439.4mm x 132.1mm)
Weight
50 lbs (22.7kg)
Ac Output Connector
6 NEMA 6-15/20R and 2 NEMA L6-20R
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Model #: SU3000RTXL3UHV
SmartOnline 3kVA On-Line Double-Conversion UPS, 3U Rack/Tower, 208/240V NEMA outlets
Description
with an installed depth of 20 inches (50.8cm). Expandable battery runtime with optional BP72V15-2U (limit 1) and BP72V28RT3U (multi-pack
compatible) external battery packs. Full time sine wave 200/208/220/230/240V AC output with +/-2% voltage regulation. Online, double-conversion
Uninterruptible Power Supply (UPS) actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered
AC output. Operates continuously without using battery power during brownouts to 130V and overvoltages to 275V. NEMA L6-20P input plug.
NEMA 6-15/20R & L6-20R output receptacles. Network-grade AC surge and noise suppression. Zero transfer time between AC and battery
operation. Network management interfaces support simultaneous communications via DB9 serial port and SNMPWEBCARD slot. Built-in DB9 port
offers both enhanced RS-232 enabled monitoring data, plus contact closure monitoring ability. Supports simultaneous detailed monitoring of
equipment load levels, self-test data and mains power conditions via all network interfaces. Includes PowerAlert monitoring software and complete
cabling. Integrated two bank PDU switching supports load shedding and remote-reboot of connected equipment. Multi-stage metered current
monitoring and battery charge status LEDs. Mains power and voltage regulation LEDs. Audible Alarm. Self-test. Fault-tolerant auto-bypass mode. 4
post rackmount accessories included; 2-9USTAND tower kit and 2POSTRMKITWM 2-post rackmount accessories available. Field replaceable, hot
swappable internal batteries and external battery packs. Attractive all-black UPS design. 2-year warranty and $250,000
insurance; extended warranty and service contracts available.
Package Includes
Features
3000VA / 3kVA on-line, double-conversion UPS system for critical server, network and telecommunications equipment. 3U rackmount form factor
SU3000RTXL3UHV Rack-Tower UPS System
PowerAlert Software and cabling
Mounting hardware for 4 post rackmount enclosures/tower stands included
Warranty information
Instruction manual
True on-line, double conversion UPS provides pure, sine wave AC output at all times
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems
Accepts input voltages between 160 and 275 (130 to 275 at loads under 70%), regulating output to selectable 200/208/220/230/240V +/-2%
3000VA/2400 watt power capacity with 8 total outlets (6 NEMA6-15/20R & 2 NEMAL6-20R)
Standard internal battery set provides 14 minutes runtime at half load
Expandable runtime with multiple external battery packs (part# BP72V15-2U limit 1/BP72V28-3U multi-pack compatible)
Innovative design makes unit adaptable for rackmount, tower, or stacking applications
Uses only 3 rack spaces (3U) in standard 19 inch rack
DB9 serial port for network interface; SNMP compatible
Slot for optional SNMP/web card (part# SNMPWEBCARD)
PowerAlert unattended shutdown software and 6 ft. network cable included
Compatible with Tripp Lite's Watchdog Service Monitoring/Reboot Software
Highlights
3000VA / 3kVA / 2400 watt on-line double-conversion 3U rack/tower UPS
208/240V +/-2% output at 50/60Hz
Expandable runtime, Hot-swappable battery modules
RS232 port; support for SNMP/WEB card options
Front panel status LEDs with detailed load and battery metering
NEMA L6-20P input; 6-15/20R & L6-20R outlets
E-mail:
Telephone: +(773) 869 1234
connected equipment
Chicago, IL 60609 USA
saleshelp@tripplite.com
1111 West 35th Street
Tripp Lite

Related parts for SU3000RTXL3UHV

SU3000RTXL3UHV Summary of contents

Page 1

... Attractive all-black UPS design. 2-year warranty and $250,000 insurance; extended warranty and service contracts available. Package Includes SU3000RTXL3UHV Rack-Tower UPS System PowerAlert Software and cabling Mounting hardware for 4 post rackmount enclosures/tower stands included Warranty information ...

Page 2

... Compatible with Tripp Lite's Watchdog Service Monitoring/Reboot Software Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions Diagnostic LEDs Battery replacement door Mounting hardware included for 4 post rack enclosures, 2 post telecom rack compatible with separate purchase 2POSTRMKITWM accessory ...

Page 3

Input circuit breaker 25A double pole UPS Input cord length 10 (ft.) UPS Input cord length 3 (m) Recommended 20A Electrical Service BATTERY Full load runtime 5 min. (2400w) (minutes) Half load runtime 14 min. (1200w) (minutes) Expandable battery Supports ...

Page 4

UPS AC suppression Instantaneous response time EMI / RFI AC noise Yes suppression PHYSICAL Installation form 2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND) factors supported with optional accessories Optional mounting Wallmount installation not recommended accessory notes Primary form factor Rackmount UPS ...

Page 5

Battery mode BTU / 1219.3 hr. (full load) COMMUNICATIONS Communications DB9 Serial; Contact closure; Slot for SNMP/Web interface interface Network monitoring Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure port description communications ...

Page 6

... More information, including related products, owner's manuals, and additional technical specifications, can be found online at www.tripplite.com/en/products/model.cfm?txtModelID=2568. Copyright © 2011 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos may differ slightly from final products. ...