SU5000RT3U Tripp Lite, SU5000RT3U Datasheet - Page 2

UPS SMARTONLINE 5KVA 3500W 16OUT

SU5000RT3U

Manufacturer Part Number
SU5000RT3U
Description
UPS SMARTONLINE 5KVA 3500W 16OUT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
Power Supply Regulatorr
Datasheet

Specifications of SU5000RT3U

Power - Rated
5kVA / 3500W
Ac Outlets
16 (UPS)
Features
DB9 Communications, SNMP Card Slot
Backup Time - Max Load
8 minutes
Voltage - Output Per Connector
208V
Voltage - Input
208V / 30A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA L6-30P
Connector - Ac Output
1 NEMA L6-30R, 2 NEMA L6-20R and 8 NEMA 5-15/20R
Size
26.00" L x 17.50" W x 5.25" H (660.4mm x 444.5mm x 133.4mm)
Weight
42 lbs (19.1kg)
Ac Output Connector
1 NEMA L6-30R, 2 NEMA L6-20R and 8 NEMA 5-15/20R
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
Output kVA capacity
(kVA)
Output Watt Capacity
(watts)
Output kW capacity
Output power factor
Crest Factor
Nominal Output
Voltage(s) Supported
Frequency compatibility
Frequency
compatibility details
Output voltage
regulation (line mode)
Output voltage
regulation (Economy
line mode)
Output voltage
regulation (Battery
mode)
Built-in UPS output
receptacles
Output circuit breaker
harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
Provides perfectly regulated, sine wave output power free of line noise, transient surges and frequency variation for the most efficient
operation of critical servers, networking and telecommunications equipment
Accepts input voltages between 156 and 276, regulating output within 2% of 208 - plus 120V nominal voltage
Supports connected equipment during blackouts for 20/8 minutes at half/full load levels, runtime is further expandable with optional external
battery packs
Network interfaces support simultaneous communications via 2 DB9 ports and SNMPWEBCARD slot
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge
current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control
Built-in Emergency Power Off (EPO) interface with cable
Includes 17 built-in output receptacles (3 L6-30R w/one L6-30R used for transformer connection, 2 L6-20R, 12 NEMA 5-15/20R)
L6-30P input plug-in connection
Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical
conditions
Front panel switches enable power on/off control, self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures, optional 2POSTRMKITWM supports 2 post
rackmount installation
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
2 year manufacturer's product warranty, $250,000
5000
5
3500
3.5
0.7
3:1
120V; 208V
50 / 60 Hz
Output frequency matches input nominal on startup
+/- 2%
+/- 10%
+/- 2%
12 5-15/20R outlet(s); 2 L6-20R outlet(s); 2 L6-30R outlet(s)
20A breakers (x4) on transformer module protect 3 5-15/20R outlets each, 20A breaker on power module protects
L6-20R outlets, L6-30R outlets are unbreakered
Ultimate Lifetime Insurance
(USA & Canada only)

Related parts for SU5000RT3U