SU30K3/3 Tripp Lite, SU30K3/3 Datasheet - Page 3

no-image

SU30K3/3

Manufacturer Part Number
SU30K3/3
Description
UPS SMARTONLINE 30KVA 24KW IGBT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
UPSr
Datasheet

Specifications of SU30K3/3

Power - Rated
30kVA / 24000W
Backup Time - Max Load
5 minutes
Voltage - Output Per Connector
120/208V 3 Phase
Voltage - Input
120 / 208V / 90A per phase (3 phase)
Ac Input Connector
Hardwire
Connector - Ac Output
None (Hardwire)
Size
26.00" L x 15.00" W x 34.00" H (660.4mm x 381.0mm x 863.6mm)
Weight
662 lbs (300.3kg)
Ac Output Connector
Hardwire
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Features
-
Cord Length
-
Ac Outlets
-
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Output AC waveform
(battery mode)
INPUT
Rated input current
(at maximum load)
Nominal Input
Voltage(s) Supported
UPS input connection
type
UPS input connection
description
BATTERY
Full load runtime
(minutes)
Half load runtime
(minutes)
Expandable battery
runtime
External battery pack
compatibility
Expandable runtime
description
DC system voltage
(VDC)
Battery recharge rate
(included batteries)
Replacement battery
cartridge (internal
UPS battery
replacement)
Battery Access
Battery replacement
description
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage
correction
Undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Front panel LCD
display
Alarms
Pure Sine wave
90A (per phase, online)
120V / 208V 3 phase wye
Hardwire
120/208V (3-Phase, 4 Wire, wye)
5 min. (24kw)
13 min. (12kw)
Supports extended runtime with optional external battery packs
SURBC2030;
Includes a battery housing with space for 1 optional
runtime capacity is available by adding
specific recommendations
240
2 - 4 hours from 10% to 90%
SURBC2030
Front panel internal battery access door
Hot-swappable, replaceable batteries
Online, double-conversion power conditioning
Maintains continuous operation without using battery power during overvoltages to 144 / 250 (3-Phase, 4-Wire,
wye), reducing output within 2% of nominal
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 96 / 166
(3-Phase, 4-Wire, wye)
7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and
battery operation
SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions including
operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and
more (see manual)
Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more
SUBF2030
(holds 4 SURBC2030)
SUBF2030
and additional
SURBC2030
battery pack for extended runtime. Additional
SURBC2030
batteries - see runtime chart for

Related parts for SU30K3/3