S8PS-05012CD Omron, S8PS-05012CD Datasheet - Page 6

POWER SUPPLY 12V 4.2A DIN RAIL

S8PS-05012CD

Manufacturer Part Number
S8PS-05012CD
Description
POWER SUPPLY 12V 4.2A DIN RAIL
Manufacturer
Omron
Series
S8PSr
Datasheet

Specifications of S8PS-05012CD

Voltage - Output
12V
Number Of Outputs
1
Power (watts)
50W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 264VAC
Mounting Type
DIN Rail
1st Output
12 VDC @ 4.2A
Size / Dimension
5" L x 1.57" W x 3.35" H (127mm x 40mm x 85mm)
Power (watts) - Rated
50W
Operating Temperature
-10°C ~ 55°C
Efficiency
80%
Approvals
CSA, EN, UL, VDE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8PS05012CD
Z1174
■ Overload Protection
50- to 300-W Models
The Power Supply is provided with an overload protection function
that protects the power supply from possible damage from an
overload. The protection function operates when the load current
rises above an overcurrent detection value (105% of the rated load
current except for 300-W models, for which the value is 101%). For a
short-circuit or overload lasting less than 20 seconds, output voltage
is decreased to protect equipment. When the output current falls
within the rated range, the overload protection function is
automatically cleared.
50-, 100-, 150-W Models
300-W Model
The valves shown in the above diagrams are for reference only.
Note: If a short-circuit or overload lasts 20 seconds or longer, internal
600-W Model
If the overload state continues for 5 seconds or longer, the output will
shut off and the protection-ON alarm indicator will simultaneously
light. Reset the input power by turning it OFF for at least one minute
and then turning it back again.
Note: Internal parts may occasionally deteriorate or be damaged if a
0
0
0
Intermittent operation
Intermittent operation
circuits may deteriorate or be damaged.
short-circuited or other overcurrent state continues during op-
eration.
50
50
50
Output current (%)
Output current (%)
Output current (%)
100
100
100
http://www.ia.omron.com/
Output
shut off
AC input
voltage
AC input
current
■ Overvoltage Protection
The Power Supply is provided with an overvoltage protection function
that protects the Power Supply from possible damage by
overvoltage. When the output voltage rises above a set value (115%
of the rated output voltage), the protection function is triggered,
shutting OFF the output voltage. Reset the input power by turning it
OFF for at least one minute and then turning it back again.
The valves shown in the above diagram are for reference only.
300- and 600-W Models
If more than approx. 115% of the rated output voltage is output, the
output will be shut off and simultaneously the protection-ON alarm
indicator will light. Reset the input power by turning it OFF for at least
one minute and then turning it back again.
■ Overheat Protection Function
600-W Model Only
If the internal temperature of the S8PS rises excessively as a result
of fan failure or any other reason, the overheat protection circuit will
be triggered to protect the internal parts of the S8PS and
simultaneously a protection-ON alarm indicator will be lit. Reset the
input power by turning it OFF for at least one minute and then turning
it back again.
■ Inrush Current, Startup Time,
Output
voltage
Input ON
Hold Time
Inrush current on input application
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
Rated output
voltage
Startup time (1,000 ms max.)
0 V
Variable range
90%
Hold time (20 ms min.)
Overvoltage
protection
operating
Input OFF
S8PS
96.5%
6

Related parts for S8PS-05012CD