SWS1000L-12 TDK Corporation, SWS1000L-12 Datasheet

PWR SUP MED 12V 88A SGL OUTPUT

SWS1000L-12

Manufacturer Part Number
SWS1000L-12
Description
PWR SUP MED 12V 88A SGL OUTPUT
Manufacturer
TDK Corporation
Series
SWS1000Lr
Type
Commercialr
Datasheets

Specifications of SWS1000L-12

Power Supply Type
Switching (Closed Frame)
Voltage - Output
12V
Number Of Outputs
1
Power (watts)
1000W
Applications
Medical
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
12 VDC @ 88A
Size / Dimension
9.45" L x 5.91" W x 2.4" H (240mm x 150mm x 61mm)
Power (watts) - Rated
1056W
Operating Temperature
-20°C ~ 74°C
Efficiency
84%
Approvals
CSA, DENAN, EN, IEC, UL
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
12V
Output Current
88A
Power Rating
1056W
Input Voltage
85V AC To 265V AC / 120V DC To 350V DC
Brand/series
SWS Series
Configuration
Enclosed
Output
12 VDC @ 88 A
Power, Output
1056 W
Primary Type
AC-DC
Special Features
Parallelable, PFC, Remote On/Off, Remote Sense
Voltage, Input
85 to 265/120 to 350 VAC/VDC
Voltage, Output
12 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1793
SWS1000L12

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
SWS1000L-12
Quantity:
125
SWS-L Series
Compact and high-power AC/DC power supply

Related parts for SWS1000L-12

SWS1000L-12 Summary of contents

Page 1

SWS-L Series Compact and high-power AC/DC power supply ...

Page 2

・All specifications are subject to change without notice. ...

Page 3

... Rated Output Voltage Output Power type Series Name We are able to add conformal coating on PCB base on customer requirement for some specified applications upon request 1000W Output Current p p Model 200A SWS1000L-3 200A SWS1000L-5 88A SWS1000L-12 70A SWS1000L- SWS1000L-24 29A SWS1000L- SWS1000L-48 17 SWS1000L-60 (Exhausted cooling) ...

Page 4

SWS 600L ITEMS/UNITS Voltage Range (*3) Frequency (*3) Power Factor (115/230VAC) (typ) (*2) Input Effi ciency (115/230VAC) (typ) (*2) Current (115/230VAC) (typ) (*2) Inrush Current (typ) (*4) Leakage Current (*10) mA Nominal Voltage Maximum Current (Peak Current) (*1) Maximum Power ...

Page 5

SWS 600L SWS600L Outline Drawing 3-M4 (45) INPUT TERMINAL NAME PLATE DC ON INDICATOR OUTPUT VOLTAGE CN2 ADJUSTMENT CN1 CN3 TERMINAL COVER 18.6 4-M5 OUTUT TERMINAL NAME PLATE (SCALE : SEE NOTE 1 SEE NOTE 2 NOTES: ...

Page 6

... However, it may not fulfi l all the specifi cations. (*13) Category 4 exposure levels: Trunk transportation over U.S. highways, composite two-wheeled trailer. (*14) As for DENAN, designed to meet at 100VAC. 6 SWS1000L Specifications MODEL SWS1000L-3 SWS1000L-5 SWS1000L-12 SWS1000L-15 SWS1000L-24 SWS1000L-36 SWS1000L-48 SWS1000L-60 V AC85-265 or DC120-350 Hz × ...

Page 7

... SWS 1000L SWS1000L Outline Drawing ( 16.7 ) 4-M4 NAME PLATE CN3 LED CN2 CN1 OUTPUT TERMINAL (-) OUTPUT TERMINAL (+) ( 14 50 NAME PLATE == SWS1000L-24 INPUT :100-240VAC ∼ 13. 60Hz OUTPUT : 24V 44 A PEAK : 51A BARCODE BAUART GEPRÜFT SEE NOTE A TÜV TYPE Rheinland APPROVED ...

Page 8

... N FG SWS600L * INPUT VOLTAGE RANGE : 85 ∼ 265VAC * FUSE RATING : 15A * PFC FREQUENCY : 100kHz BOOST MODE * DC-DC FREQUENCY : 300kHz FORWARD SWS1000L * INPUT VOLTAGE RANGE : 85 ∼ 265VAC * FUSE RATING : 20A * PFC FREQUENCY : 130kHz BOOST MODE * DC-DC FREQUENCY : 200kHZ FORWARD AC Input 0V Vout Output voltage ...

Page 9

... SELV. If the outputs are not earthed, they must be considered hazardous and must not be made user accessible. The output and control terminals of SWS600L-48 and SWS600L-48 / RF, SWS1000L-48 and SWS1000L48/RF are ELV. The output and control terminals of SWS600L-60 and SWS600L-60 / RF, SWS1000L-60 and SWS1000L60/RF are hazardous voltage ...

Page 10

... AC input terminal L : Live line (Fuse in line), M4 screw. ⑥ AC input terminal N : Neutral line, M4 screw. ⑦ Output terminal (SWS600L: M5 screw SWS1000L:φ9hall, M4 tapped hall x 2) ⑧ Output terminal (SWS600L: M5 screw SWS1000L:φ9hall, M4 tapped hall Terminal Explanation C N1 Configuration and Function CN1 and CN2 are same pin confi guration and function. They are connected to each other in this power supply unit ...

Page 11

... A CN1(or CN2) B ・All specifications are subject to change without notice. SWS1000L ter- ● ALM signal output required Open collector method shown below shall be used. “G1” terminal is ground for “ALM” terminal. SWS600L SWS1000L A twist or shield B A CN1(or CN2) A twist or shield B B CN3 ...

Page 12

SWS 600L, 1000L Input Voltage Range Input voltage range is single phase 85 - 265VAC (47 - 63Hz) or 120 - 350VDC. Input voltage, which is out of specifi cation, may cause unit damage. Rated input voltage for safety standard ...

Page 13

SWS 600L, 1000L (a) AUX 2.2KΩ CNT1 150Ω CNT2 12V typ TOG G2 Example V1:5V R1:620Ω) (b) AUX 2.2KΩ CNT1 150Ω CNT2 12V typ TOG G2 (c) 2.2KΩ 150Ω 12V typ Fig.2.3 Examples of connecting remote ON/OFF circuit Output Ripple ...

Page 14

... Tester 14 Output - CNT・AUX・ALM : 100VDC 50MΩ or more Load Withstand Voltage SWS600L is designed to withstand 3.0kVAC, SWS1000L is de- signed to withstand 4.0kVAC between input and output. This series is designed to withstand 2.0kVAC between input and (chassis), 500VAC between output and 100VAC between output and CNT, AUX, ALM terminal each for Load 1 minute ...

Page 15

SWS 600L, 1000L Output - CNT· AUX · ALM : 100VAC 1min. (100mA) +S AC(L) +Vm + AC( COM PV CNT1 CNT2 TOG ALM AUX G1 G2 Output Voltage External Control (PV) Output voltage external control ...

Page 16

... V.ADJ Output Derating OUTPUT DERATING CURVE 100 80 60 Mounting -20 - ( ℃) Load (%) Ta(℃ ) Mounting *Output derating for both SWSS600L and SWS1000L 16 5. Mounting Directions 100 (C) Mounting (F) Inhibit 100 (C) Mounting (F) Inhibit 0 V.ADJ + + Mounting Method (1) Forced air cooling type power supply. ...

Page 17

... Recommended torque for the terminal : SWS600L Input terminal (M4 screw) : 1.27 N · m (13.0kgf · cm) Output terminal (M5 screw) : 2.5 N · m (25.5kgf · cm) SWS1000L Input terminal (M4 screw) : 1.27 N · m (13.0kgf · cm) Output terminal (M8 bolt & nut) : 10.8 N · m (110kgf · cm) (M4 screw) : 1.27 N · m (13.0kgf · cm) [The PHD connector manufacture method] This product is using SPHD-001T-P0 ...

Page 18

... Connect only apparatus complying with IEC/EN/UL60601-1 to the signal ports External Fuse Rating 8. Fan life expectancy Fan acoustic noise: SWS600L, SWS1000L: build in fan speed control circuit . SWS600L : 45dB[A] at room temperature, 50dB[A] at high SWS1000L: 53dB[A] at room temperature, 55dB[A] at high SWS600L/RF: 50dB[ 100 0 (5) Except for permanently installed equipment as defi ...

Page 19

SWS 600L, 1000L 10. Before concluding that the unit is at fault Before concluding that the unit is at fault, make the following checks. (1) Check if the rated input voltage is connected. (2) Check if the wiring of input ...