ZUP80-2.5/U TDK Corporation, ZUP80-2.5/U Datasheet - Page 29

PWR SUP BENCH PROG 0-80V 200W

ZUP80-2.5/U

Manufacturer Part Number
ZUP80-2.5/U
Description
PWR SUP BENCH PROG 0-80V 200W
Manufacturer
TDK Corporation
Series
ZUPr
Datasheets

Specifications of ZUP80-2.5/U

Voltage - Output
0 ~ 80V
Number Of Outputs
1
Power (watts)
200W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 80 VDC @ 2.5A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
200W
Operating Temperature
0°C ~ 50°C
Efficiency
82%
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.01%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Other names
285-1685
ZUP802.5/U
Table 4-1: Front panel controls and indicators
1
2
3
4
5
9
6
7
8
#
AMPS Display
VOLTS Display
CV Indicator
CC Indicator
ADJUST knob
ALM Indicator
(Rotary pulse generator)
OUT Pushbutton
REM Pushbutton
FOLD Pushbutton
Control/Indicator
Description
Actual output current display at normal operation. While
adjusting the output current, the set value will be shown.
The display will automatically return to show the actual
current approx. 3sec from completion of adjustment.
Actual output voltage display at normal operation. The
measurement circuits monitor the voltage at the sensing
points, hence at remote sensing where there is voltage
drop on the load wires, the voltage at the power supply
output terminals will be higher than the displayed value.
Attention should be taken not to exceed the output power
rating. While adjusting the output voltage, the set value will
be shown. The display will automatically return to show the
actual voltage approx. 3sec after completion of adjustment.
CV LED indicates that the power supply is regulating it’s
output at a constant voltage.
CC LED indicates that the power supply is regulating it’s
output at a constant current.
The ADJUST knob functions to determine the following
output parameters:
1. Output voltage adjust - as determined by V/A pushbutton
2. Output current adjust - as determined by V/A pushbutton
3. Over voltage protection adjust - as determined by
4. Under voltage soft limit adjust-as determined
5. Address selection
ALM indicates alarm caused by activation of one of the
following protections:
* Over voltage protection
* Over temperature protection
* Foldback protection
Main function: Enable or disable the power supply output.
Auxiliary function: Press and hold OUT pushbutton for
approx. 3sec to change function to select between safe
mode restart and automatic restart.
Main function: Select between local or remote operation.
Auxiliary function: Press and hold REM pushbutton for
approx. 3sec to change function to select between RS232
or RS485 communication.
Pressing FOLD pushbutton arms foldback protection
which shuts down output if supply transits from CV to CC.
OVP/UVP pushbutton
by OVP/UVP pushbutton
5.2.1
4.4.2
4.4.3
4.4.5
4.4.6
4.4.7
5.2.4
4.4.8
4.4.9
Par.