ZUP36-12/U TDK Corporation, ZUP36-12/U Datasheet - Page 48

PWR SUP BENCH PROG 0-36V 432W

ZUP36-12/U

Manufacturer Part Number
ZUP36-12/U
Description
PWR SUP BENCH PROG 0-36V 432W
Manufacturer
TDK Corporation
Series
ZUPr
Type
Enclosedr
Datasheets

Specifications of ZUP36-12/U

Number Of Outputs
1
Efficiency
84%
Voltage - Output
0 ~ 36V
Power (watts)
432W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 36 VDC @ 12A
Size / Dimension
13.78" L x 4.88" W x 2.76" H (350mm x 124mm x 70mm)
Power (watts) - Rated
432W
Operating Temperature
0°C ~ 50°C
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.01%
Output Current (max)
12A
Input Voltage
85 to 265V
Input Frequency
47 to 63Hz
Screening Level
Commercial
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
50C
Mounting Style
Desktop
Accuracy
0.02% + 20 mV
Brand/series
ZUP
Current, Output
12 A
Display Type
Digital Meter
Power, Output
432 W
Power, Rating
432 W (Max.)
Regulation, Line
0.01% + 2 mA⁄1 mV + 0.005%
Regulation, Load
0.01% + 5 mA⁄2 mV + 0.005%
Standards
UL Listed, CE Marked
Temperature Coefficient
30 ppm⁄°C (CV)⁄100 ppm⁄°C (CC)
Temperature, Operating, Maximum
50 °C
Temperature, Operating, Minimum
0 °C
Voltage, Input
85-265 VAC
Voltage, Noise
50 mV @ 20 MHz BW
Voltage, Output
36 VDC
Voltage, Ripple
5 mV @ 5 Hz to 1 MHz
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1676
ZUP3612/U
5.5.2 ID control commands
5.5.1 Initialization control
4
3
#
1
2
#
1
2
:ADRn;
:RMT?;
Commands
Commands
:RMTn;
:MDL?;
:REV?;
:DCL;
Returns the remote/local setting. The returned data is an ASCII string.
RM1 (The unit is in remote mode)
RM2 (The unit is in latched remote mode)
Sets the power supply address. ADR is followed by the address
which can be 01 to 31.
Sets the power supply to local or remote mode. (This command is active
when the unit is either in Local or Remote modes).Transition from Local to
Remote mode is made via the front panel only.
:RMT0; Transition from Remote to Local mode.
:RMT1; Transition from latched Remote to non-latched Remote.
:RMT2; Latched remote: Transition back to Local mode or to non- latched
Remote can be made via the serial port (RS232/485).
At this mode, the front panel Local/Rem function is disabled. Escape from
this mode to non -latched remote mode can be made by turning the AC
ON/OFF to OFF and after approx. 10sec.to ON again.
Returns the power supply model identification as an ASCII string:
Nemic-Lambda ZUP(XXV)-(YYA).
XX - The rated output voltage
YY - The rated output current
example: Nemic-Lambda ZUP(6V-33A)
Returns the software version as an ASCII string:
Ver XX-YYA.B
XX- The rated output voltage
YY- The rated output current
A.B- Version identifier
example: Ver 6-33 1.0
Clears the communication buffer and the following registers:
1. Operational status register
2. Alarm (fault) status register
3. Programming error register
Description
Description