ZUP6-132/U TDK Corporation, ZUP6-132/U Datasheet - Page 50

PWR SUP BENCH PROG 0-6V 792W

ZUP6-132/U

Manufacturer Part Number
ZUP6-132/U
Description
PWR SUP BENCH PROG 0-6V 792W
Manufacturer
TDK Corporation
Series
ZUPr
Datasheets

Specifications of ZUP6-132/U

Voltage - Output
0 ~ 6V
Number Of Outputs
1
Power (watts)
792W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
0 ~ 6 VDC @ 132A
Size / Dimension
13.78" L x 5.51" W x 4.88" H (350mm x 140mm x 124mm)
Power (watts) - Rated
792W
Operating Temperature
0°C ~ 50°C
Efficiency
77%
Approvals
CE, EN, UL
Line Regulation
0.01%
Load Regulation
0.07%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Other names
285-1682
ZUP6132/U
5.5.3 Output control continued
10
12
11
#
5
6
7
8
9
:CUR!;
:CUR?;
:OVPn;
Commands
:FLD?;
:OVP?;
:OUTn;
:OUT?;
:FLDn;
Example - ZUP10-XY :OVP08.4;
Example- OP08.4
Description
Returns the string
output current. The programmed value range is shown in table 5-2.
example- SA3.000 SA07.50
Returns the string
The actual current range is the same as the programming range.
example- AA3.000 AA07.50
Sets the output to On or Off.
:OUT1; - Output On
:OUT0; - Output Off
Returns
OT1 - Output is On
OT0 - Output is Off
Sets the Foldback protection to On or Off.
:FLD1; Arm the foldback protection.
:FLD0; Release the foldback protection.
:FLD2; Cancel the foldback protection.
When the foldback protection is activated, :FLD0; will release the
protection and re-arm it while :FLD2; will cancel the protection. If the
protection has not been activated, both commands are the same.
Returns
FD1 - Foldback is armed
FD0 - Foldback is released
Sets the over-voltage protection level in volts. Over-voltage range settings
are given in table 5-3:
Table 5-3: Over-voltage programming range.
Returns the string
protection value. The over-voltage range is given in table 5-3.
ZUP6-XY
ZUP10-XY
ZUP20-XY
ZUP36-XY
ZUP60-XY
Model
ZUP80-XY
ZUP120-XY 006.0 132.0
OT
FD
followed by the Foldback protection status.
followed by the output On/Off status.
MIN.
0.20
00.5
01.0
01.8
03.0
04.0
AA
OP
SA
MAX.
13.0
24.0
40.0
66.0
88.0
(Actual Amper) followed by the actual output current.
7.50
(Set Amper) followed by the present programmed
followed by the present programmed over-voltage

Related parts for ZUP6-132/U