2938248 Phoenix Contact, 2938248 Datasheet - Page 3

POWER SUPPLY 10A 100-240AC 48DC

2938248

Manufacturer Part Number
2938248
Description
POWER SUPPLY 10A 100-240AC 48DC
Manufacturer
Phoenix Contact
Series
Quintr
Type
Industrialr
Datasheets

Specifications of 2938248

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
480W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
48 VDC @ 10A
Size / Dimension
4.92" L x 6.18" W x 5.12" H (125mm x 157mm x 130mm)
Power (watts) - Rated
480W
Operating Temperature
-25°C ~ 70°C
Efficiency
90%
Approvals
CB, cUL, GOST UL
Product
Switching
Commercial/medical
Commercial
Output Power Rating
480 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
48 VDC
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Brand/series
QUINT-PS
Configuration
Enclosed
Operation
Switching
Output
48 VDC @ 10 A
Phoenix Part Number
QUINT-PS-100-240AC/48DC/10
Power, Output
56 W
Primary Type
AC-DC
Voltage, Input
85 to 264/90 to 350 VAC/VDC
Voltage, Output
48 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-1914
QUINT-PS-100-240AC/48DC/10
QUINT-PS-100-240AC/48DC/10
PHOENIX CONTACT Inc., USA
Peak switching voltages nominal load
Maximum power dissipation idling
Power loss nominal load max.
General data
Width
Height
Depth
Weight
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Mounting position
Assembly instructions
Electromagnetic compatibility
Immunity to interference
Standard – Electrical equipment of machines
Standard – Safety transformers for switched-mode
power supply units
Standard - Electrical safety
Standard – Shipbuilding
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
Standard – Safety extra-low voltage
Standard - Safe isolation
Standard – Protection against electric shock
Order No.: 2938248
< 50 mVPP
5 W
56 W
157 mm
130 mm
125 mm
2.5 kg
> 90 %
4 kV AC (type test)
2 kV AC (routine test)
IP20
I, with PE connection
> 500 000 h in acc. with IEC 61709 (SN 29500)
-25 °C ... 70 °C (> 60°C derating)
-40 °C ... 85 °C
95 % (at 25°C, no condensation)
Horizontal DIN rail NS 35, EN 60715
Can be aligned: Horizontal 0 cm, vertical 5 cm
Conformance with EMC directive 89/336/EEC
EN 61000-6-2
EN 60204
EN 61558-2-17
EN 60950/VDE 0805 (SELV)
EN 61558-2-17
German Lloyd, ABS
EN 50178/VDE 0160 (PELV)
EN 60950 (SELV)
EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN 57100-410
Page 3 / 7