FE1000-48NA TDK Corporation, FE1000-48NA Datasheet

no-image

FE1000-48NA

Manufacturer Part Number
FE1000-48NA
Description
POWER SUPPLY COMPACT RACK MOUNT
Manufacturer
TDK Corporation
Series
FEr
Datasheet

Specifications of FE1000-48NA

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 21A
Size / Dimension
11.97" L x 5" W x 3.3" H (304mm x 127mm x 83.8mm)
Power (watts) - Rated
1000W
Operating Temperature
-40°C ~ 70°C
Efficiency
82%
Approvals
CE, CSA, EN, IEC, UL
Line Regulation
±1%
Load Regulation
±1%
3rd Output
-
2nd Output
-
4th Output
-
Other names
Q1001884
FE S
I
M
ERIES
NSTRUCTION
ANUAL
Thank you for purchasing a Lambda FE Series power module. The FE Series represents
the most power dense front-end power modules currently available and offers many
advantages that abet use in telecommunication, process control, photonics and computer
applications.
Electrical specifications pertaining to FE power modules are included in the following
matrices as well as sense and signaling connection information. Please note that for the
FE power module to function properly, the proper connections must be made on the 25-
pin connector. These connections are described in the Sense and Signaling matrices for
both stand-alone module use and for modules assembled in a standard FE Series racking
system.
In order to function optimally, the following mating connectors should be used for
modules utilized in a stand-alone configuration:
FE Power Module AC Input Power Interface
FE0500 and FE1000 modules utilize a 15 ampere IEC 320 male receptacle and FE1500 and
FE2000 modules utilize a 20 ampere IEC 320 male receptacle. Mating connectors can,
respectively, be obtained from the following sources:
Panel Components Corporation
P.O. Box 6626
Santa Rosa, CA 95406
800-662-2290 (telephone)
FE0500, FE1000 — PCC Model No. 86525032
Qualteck Electronics Corporation
7676 Jenthers Drive
Mentor, OH 44060
216-951-3300 (telephone)
FE1500 — Qualteck Model No. 227003-01
FE2000 — Qualteck Model No. 225003-01
FE Power Module DC Output Power Interface
FE Series power modules utilize Iccon-style connectors as an output interface. For stand-alone
use, Lambda recommends the following board-mount pin mating connectors be used:
Elcon Products
P. O. Box 1885
Fremont, CA 94538
510-490-4200 (telephone)
FE0500, FE1000 — require two Elcon Model No. 259-16-00100 per module
FE1500, FE2000 — require four Elcon Model No. 259-16-00100 per module
LAMBDA ELECTRONICS INCOPORATED
515 BROAD HOLLOW ROAD, MELVILLE, NY 11747-3700 • TEL: 516-694-4200 • 516-293-0519
P. 1
IMFE1000

Related parts for FE1000-48NA

FE1000-48NA Summary of contents

Page 1

... FE Power Module AC Input Power Interface FE0500 and FE1000 modules utilize a 15 ampere IEC 320 male receptacle and FE1500 and FE2000 modules utilize a 20 ampere IEC 320 male receptacle. Mating connectors can, respectively, be obtained from the following sources: Panel Components Corporation P ...

Page 2

... Please feel free to contact Lambda at 1-800-Lambda-4 if you have any questions regarding your FE Series power modules and thank you for your purchase. LAMBDA ELECTRONICS INCOPORATED 515 BROAD HOLLOW ROAD, MELVILLE, NY 11747-3700 • TEL: 516-694-4200 • 516-293-0519 I M ERIES NSTRUCTION ANUAL P. 2 IMFE1000 ...

Page 3

... FE S RATINGS AND SPECIFICATIONS FOR LAMBDA MODEL NO. FE1000: I. MAXIMUM RATINGS SPECIFICATION UNITS OUTPUT VOLTAGE RANGE OUTPUT CURRENT (POWER) A (W) AT 50ºC ( OUTMIN OUTPUT CURRENT (POWER) A (W) AT 60ºC ( OUTMIN OUTPUT CURRENT (POWER) A (W) AT 70ºC ( OUTMIN OPERATING TEMPERATURE ºC II. INPUT SPECIFICATIONS ...

Page 4

... FROM AC INPUT TO AUXILIARY SIGNALS. THE CURRENT MONITOR SIGNAL IS REFERENCED TO THE -IMON TERMINAL (THE CATHODE OF THE INTERNAL OR-ING DIODE.) LAMBDA ELECTRONICS INCOPORATED 515 BROAD HOLLOW ROAD, MELVILLE, NY 11747-3700 • TEL: 516-694-4200 • 516-293-0519 I M ERIES NSTRUCTION ANUAL OPERATIONAL DEFINITION OPERATIONAL DEFINITION OPERATIONAL DEFINITION P. 4 TERMINAL. OUT IMFE1000 ...

Page 5

... TO +70 WITH DERATING ABOVE +50 (-40 OPERATION REQUIRES A THIRTY MINUTE WARM-UP PERIOD) 11.97 x 5.00 x 3.30 BLACK EITHER STAND-ALONE OR ASSEMBLED INTO A STANDARD LAMBDA MODEL NO. FE5K RACKING SYSTEM. DEFINITION TERMINAL PROVIDE A SINGLE POINT FAILURE RIDE-THROUGH FOR FE1000-48 8.25 9.25 TERMINAL FOR OUT IMFE1000 ...

Page 6

... COLLECTOR OF THE INTERNAL OPTO-TRANSISTOR CAPABLE OF SINKING UP TO 5mA WITH 20 VOLTS MAXIMUM APPLIED FROM COLLECTOR TO EMITTER. OPEN COLLECTOR SIGNAL INDICATING THAT AN OVERTEMPERATURE CONDITION HAS OCCURRED. THIS PIN REPRESENTS THE COLLECTOR OF THE INTERNAL OPTO-TRANSISTOR CAPABLE OF SINKING UP TO 5mA WITH 20 VOLTS MAXIMUM APPLIED FROM COLLECTOR TO EMITTER IMFE1000 ...

Page 7

... FE S Lambda FE Series Safety and Installation Instructions for Lambda Model FE1000 To comply with published safety standards, the following instructions must be used in conjunction with the Lambda FE Series: For earth fault protection, the unit must be protected in the final installation by suitable overcurrent protection means. If protection relies upon building wiring, the end product installation must ensure that the necessary protection is provided ...

Page 8

... FE S Sicherheits und Installationsanleitung für Lambda Modell FE1000 Die folgende Sicherheitshinweise müssen bei der Verwendung der Netzteile beachtet werden: Gegen Isolationsfehler zum Schutzleiter muß in der Endanwendung eine angemessene Absicherung vorgenommen werden. Falls die Absicherung durch die Gebäudeinstallation erfolgt, muß beim Einbau in das Endgerät entsprechend darauf hingewiesen werden. ...

Page 9

... ERIES NSTRUCTION LAMBDA ELECTRONICS INCOPORATED 515 BROAD HOLLOW ROAD, MELVILLE, NY 11747-3700 • TEL: 516-694-4200 • 516-293-0519 ANUAL IMFE1000 ...

Related keywords