MODULE I/O AC OUT 3A 15VDC IN

G3TC-OAC15A DC15

Manufacturer Part Number
G3TC-OAC15A DC15
Description
MODULE I/O AC OUT 3A 15VDC IN
Manufacturer
Omron
Series
G3TCr
Type
ACr
Datasheet

Specifications of G3TC-OAC15A DC15

Color
Black
Style
Standard
Voltage - Input
15VDC (9 ~ 16VDC)
Current - Input
18mA
Voltage - Output
75 ~ 280VAC (240VAC Nom)
Current - Output
0.05 ~ 3A
Turn On Time
1/2 Cycle + 1ms
Turn Off Time
1/2 Cycle + 1ms
Features
Hold Down Screw
Control Voltage Range
15 VDC
Load Current Rating
3 A
Contact Form
1 Form A
Relay Type
Inupt/Output Modules
Termination Style
Solder Tail
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
G3TC-OAC15ADC15
G3TCOAC15ADC15
G3TCOAC15ADC15NC
■ Operating and Storage Environments
Operating Ambient Temperature
The rated value for the ambient operating temperature of the G3TC
is for when there is no built-up heat. For this, reason, under condi-
tions where heat dissipation is not good due to poor ventilation, and
where heat may build up easily, the actual temperature of the G3TC
may exceed the rated value resulting in malfunction or burning.
When using the G3TC, design the system to allow heat dissipation
sufficient to stay below the Load Current vs. Ambient Temperature
characteristic curve. Note also that the ambient temperature of the
G3TC may increase as a result of environmental conditions (e.g., cli-
mate, air-conditioning) and operating conditions (e.g., mounting in an
airtight panel).
Operating and Storage Locations
Do not use or store the G3TC in the following locations. Doing so
may result in damage, malfunction, or deterioration of performance
characteristics.
1. Do not use or store in locations subject to direct sunlight.
2. Do not use in locations subject to ambient temperatures outside
3. Do not use in locations subject to relative humidity outside the
4. Do not store in locations subject to ambient temperatures outside
5. Do not use or store in locations subject to corrosive or flammable
6. Do not use or store in locations subject to dust (especially iron
7. Do not use or store in locations subject to shock or vibration.
8. Do not use or store in locations subject to exposure to water, oil,
Transportation
When transporting the G3TC, observe the following points. Not doing
so may result in damage, malfunction, or deterioration of perfor-
mance characteristics.
1. Do not drop the G3TC or subject it to severe vibrations or shock.
2. Do not transport the product if it is wet.
Vibration and Shock
Do not subject the SSR to excessive vibration or shock. Otherwise
the SSR may malfunction and internal components may be dam-
aged.
the range -30° to 80°C.
range 45% to 85% or locations subject to condensation as the
result of severe change in temperature.
the range -30° to 100°C.
gases.
dust) or salts.
or chemicals.
Solid State Relays for Industrial I/O