85100435 Crouzet USA, 85100435 Datasheet - Page 2

no-image

85100435

Manufacturer Part Number
85100435
Description
RELAY SAFETY 230VAC DIN
Manufacturer
Crouzet USA
Series
KNA3-RSr
Datasheet

Specifications of 85100435

Relay Type
Safety
Contact Form
3PST (3 Form A)
Contact Rating (current)
6A
Switching Voltage
440VAC - Max
Coil Voltage
230VAC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Circuit
3PST (3 Form A)
Contact Rating @ Voltage
6A @ 250VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Coil Type
-
Coil Current
-
Control On Voltage (max)
-
Control Off Voltage (min)
-
Lead Free Status / Rohs Status
 Details
Start
Control devices :
Depending on the degree of safety required, KNA3-RS can
receive the following components as inputs :
- emergency stop pushbuttons with two contacts (Y11-Y12 and
Y21-Y22)
- position sensors (limit switches) with one or two contacts (Y11-
Y12 and Y21-Y22)
- pushbutton for start or validation (Y1-Y2)
A positive break operation device must be used if a single contact
is used.
To increase the degree of safety, one "N/C" auxiliary contact per
power contactor is wired on terminals X1-X2 to ensure self-
checking in this part of the installation.
Examples of use
Dimensions
KNA3-RS fitted with emergency stop with two channels
+ 24 Vcc
c1
c2
c3
0V
118
113
90
Y11
A1
KNA3-RS
A2
+ wired return loop.
LEVEL 4 SAFETY
13 23 33
Y12
PE
X1 Y2 S1 S2 41
X2 Y1 14 24 34
14 24 34 42
C1 C2 C3
Y21
13
Y22
23
41
33
42
45
41-42 to PLC or fault
circuit
+0,5
–0
S1 and S2 bridged for
start / validation input
protection
Emergency stop
11/9
Control devices :
The KNA3-RS has three "N/O" safety contacts (13-14/23-24/33-34) and one
"N/C" signalling contact (41-42). One or more control devices may be wired
up to the breaking capacity of the safety contacts : 1500 VA. However, to limit
internal heating in the KNA3-RS, it is advisable not to exceed 10 A thermal
for all three contacts. The signalling contact cannot be used as a safety
contact.
The signalling contact can be wired on a PLC input or integrated into a fault
signalling system.
Extending the number of contacts :
The number of contacts of the KNA3-RS can be extended and the breaking
capacity thus increased. To do this, use the KZE3-XS (see page 11/20).
Mounting - Removing see page 11/7
Compulsory :
S1 and S2 bridged
for start / validation
input protection
Start
+ 24 Vcc
c1
c2
c3
0V
KNA3-RS fitted with two cells
Y11
KNA3-RS
A1
A2
13 23 33
Y12
X1 Y2 S1 S2 41
X2 Y1 14 24 34
14 24 34 42
LEVEL 2 SAFETY
Y21
C1 C2 C3
Y22
13
23
41
33
42
41-42 to PLC or fault circuit
"Light On"
reflex cells
11