G3JA-D451B AC/DC24 Omron, G3JA-D451B AC/DC24 Datasheet

no-image

G3JA-D451B AC/DC24

Manufacturer Part Number
G3JA-D451B AC/DC24
Description
STARTR 3PHASE HYBRD 200-480V 51A
Manufacturer
Omron
Series
G3JAr
Datasheet

Specifications of G3JA-D451B AC/DC24

Circuit
3PST (3 Form A)
Output Type
AC
Load Current
51A
Voltage - Input
24VAC/DC
Voltage - Load
200 ~ 480 V
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Package / Case
Module
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G3JA-D451BAC/DC24
G3JAD451BACDC24
Built-in Bypass Relay and Smooth Motor Starts/Stops
Achieved in a Compact Starter
• Advanced functions include soft start, kick start, and soft stop.
• Phase control using a thyristor limits current when the motor starts, and a
• Controls 3-phase, 3-wire motor or 3-phase, 6-wire motor.
• Built-in electronic thermal overload relay.
• Built-in fault diagnosis for overtemperature, phase reversal, phase loss/open
• cULus listed; complies with IEC standards.
• Mounts with screws or to DIN track.
• Built-in operation/fault indicator.
• Built-in auxiliary contact for fault indication.
• Built-in auxiliary contact to output operating status.
• An Optional Auxiliary Contact Block can be added to output operating status.
Characteristics
Note: Select either voltage control start or current limit start.
Applicable Motors
Three-phase, 3-wire Motor
(Line)
The G3JA-C can be
used for a 3-phase,
3-wire motor as
shown in the
following diagram.
(Star-delta wiring for
the motor is required
if a 3-phase, 6-wire
motor is used.)
Item
Applicable
motors
Functions
bypass relay minimizes power loss while the motor is running.
load, current imbalance, and shorted SCR.
Three-phase Hybrid Soft Starter
(Soft Start, Kick Start, Current Limit Start, Soft Stop)
G3JA-C
Refer to Safety Precautions on page 16.
Rated operating voltage (motor)
Rated operating current (motor)
Applicable motor capacity
IEC 60947-4-2, 230 VAC
Voltage control start (See note.)
Kick start
Current limit start (See note.)
Soft stop
Fault detection relay output (NO)
Auxiliary contact output (NO)
Optional Auxiliary Contact Block
output
Fault detection LED indicator
Overload protection
Phase reversal detection
Current imbalance detection
Motor
Three-phase, 6-wire Motor
(Delta)
A 3-phase, 6-
wire motor
(that supports
a star-delta
operation
start) can be
used. The
G3JA-C is
compact and
includes
functionality
for devices
that start
operation with
star-delta
(
Type
3-phase, 3-lead
motor
3 to 37 A
0.55 to 7.5 kW
) wiring.
200 to 480 VAC
50/60 Hz
3-phase, 6-lead
motor (star-delta
wiring)
3 to 64 A
0.55 to 18.5 kW
(±5%)
Motor
(±10%)
Model Number Structure
■ Model Number Legend
Soft Starter
1. Controller Type
2. Rated Operating Voltage of Main Circuit
3. Rated Operating Current of Main Circuit
4. Terminal Type
5. Control Voltage
Accessories
1. Option
2. Number of Contacts
1. Option
G3JA-C@@@@
G32J-@@
G32J-@
C: Soft start/stop
4: 200 to 480 VAC, 3 phase, 50/60 Hz
03: 3 A
09: 9 A
16: 16 A
B: Screw terminals (screw clamps)
AC100-240: 100 to 240 VAC 50/60 Hz
AC/DC24:
CA: Auxiliary Contact Block
10: 1 NO
20: 2 NO
CF64: Fan
TA10: Round Terminal Block Adapter
1 2
1
1 2 3 4 5
19: 19 A
25: 25 A
24 VAC 50/60 Hz, 24 VDC
01: 1 NC
11: 1 NO/1 NC
30: 30 A
37: 37 A
CSM_G3JA-C_DS_E_5_1
1

Related parts for G3JA-D451B AC/DC24

G3JA-D451B AC/DC24 Summary of contents

Page 1

... Phase reversal detection Current imbalance detection Note: Select either voltage control start or current limit start. Applicable Motors Three-phase, 3-wire Motor Three-phase, 6-wire Motor (Line) (Delta) The G3JA-C can be A 3-phase, 6- used for a 3-phase, wire motor 3-wire motor as (that supports shown in the a star-delta following diagram ...

Page 2

... Production of a new version of the Soft Starter (version 2) with added functions was started in August 2008. The DIP switch settings of the new version are different from the previous version. For details, refer to Upgrades for Version 2 on page 13. When replacing G3JA-C (version 2) with G3JA-D, refer to “Three-phase, 6-wire Motors (Star-delta Wiring)” list above. ■ Accessories (Order Separately) ...

Page 3

... AWG), Stripping length (recommended 5 6 G3JA-C (40°C, Start time Current limit: 350% with fan used) 140 G3JA-C403/C409 120 G3JA-C416/C419 100 G3JA-C425/C430/C437 Load current (A) Model G3JA-C403 G3JA-C409 G3JA-C416 G3JA-C419 G3JA-C425 G3JA-C430 G3JA-C437 Rated breaking current Rated breaking current cULus (UL 508) G3JA-C G3JA-C425 G3JA-C430 G3JA-C437 8 12 ...

Page 4

... A at 120 VAC, 0 240 VAC Open Close: 432 VA cULus (UL 508) cULus (UL 508) 2 peak Hz, 0.19-mm single amplitude 2 peak Hz, 0.075-mm single amplitude 2 ( (15 G) G3JA-C IEC (EN/IEC 60947-4-2) III (See note.) IEC (EN/IEC 60947-4- 2,000 VAC III (See note.) AC15 IEC (EN/IEC 60947-4-2) IEC (EN/IEC 60947-4-2) 4 ...

Page 5

... Applicable Standards Safety standards UL 508 (Listing: File No. E64562), CSA 22.2 No. 14, EN/IEC 60947-4-2 cULus (UL 508) cULus (UL 508) --- --- 4 kV contact discharge and 8 kV air discharge --- --- --- G3JA-C IEC (EN/IEC 60947-4-2) IEC (EN/IEC 60947-4-2) Class A Class A Conforms to IEC 60947-4-2 Conforms to IEC 60947-4-2 Conforms to IEC 60947-4-2 5 ...

Page 6

... E-stop Normal Up-to-speed *1. This transformer is used to convert the load voltage into the control voltage of the G3JA. A transformer is not required if the load voltage is within the rated operational voltage range of the G3JA. *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta). L3 ...

Page 7

... Up-to-speed *1. This transformer is used to convert the load voltage into the control voltage of the G3JA. A transformer is not required if the load voltage is within the rated operational voltage range of the G3JA. *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta). 3 ...

Page 8

... If the motor load is extremely small, the soft stop time will be very short. G3JA-C Kick start (when selected) *2 100% Stable ...

Page 9

... LED indicator and closes the alarm contact. Shorted SCR The G3JA-C always checks the SCR for a short circuit before the starting sequence short circuit is found, the G3JA-C stops the starting sequence, indicates the short circuit with a flashing LED indicator, and closes the alarm contact ...

Page 10

... Note: Test Mode for overload testing will be entered when the Reset Button is pressed for approximately seconds. Test Mode will be cancelled when the Reset Button is pressed again. Control Terminals The G3JA-C has eight input terminals on the front. Each terminal is described in the following table. Description Terminal A1 ...

Page 11

... DIP switch pins Time (seconds OFF OFF OFF ON OFF 0.5 OFF ON 1 1.5 * Set Kick Start to OFF if the G3JA is used with a Current Limit Start. Auxiliary Contacts and Optional Auxiliary Contact Block DIP switch Optional pin 14 Auxiliary Auxiliary contacts Contact (13 to 14) Block (23 to 24) ON ...

Page 12

... Mounting Dimensions for the Auxiliary Contact Block and Round Terminal Block Adapter Trip Class 15 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) 44.8 109 141.5 10 44.8 109 23 141.5 23 G3JA-C Trip Class 20 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) (Unit: mm) Panel Cutouts 4.5 dia 46.4 132 35 3 46.4 ...

Page 13

... Soft start time settings ■ Identifying Upgraded Models You can check whether the G3JA is an upgraded version by the markings on the G3JA or the label on the box. If the G3JA is not marked “Ver. 2,” the previous version. Markings on Unit Comparison of DIP Switch Settings DIP ...

Page 14

... OFF 3. Motor Wiring Method (New Version) Optional Auxiliary Contact Block (Previous Version) Previous version DIP switch pin 15 Optional Auxiliary Contact Block ON (23 to 24) Normal OFF Up-to-speed G3JA-C New version (version 2) DIP switch pins Time (unit OFF OFF OFF OFF ON OFF 10 ON ...

Page 15

... Mounting 1. Mount the fan so that the arrow on the surface of the Fan (G32J- CF64 the direction shown in the figure. 2. Insert the fan connector into the G3JA connector until it clicks into place Mount the fan on the G3JA. Round Terminal Block Adaptor ...

Page 16

... If voltage is applied to the main circuit power supply side of the G3JA, there will be voltage in the terminals on the main circuit load side even if the G3JA is OFF. Be sure to use the warning labels included with the product to provide notification of this hazard on locations such as the motor terminal box, G3JA, and control panel. ...

Page 17

... Connecting a Power Capacitor If you use a power capacitor, connect it to the primary side (i.e., power supply side) of the G3JA output terminals. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. ...

Related keywords