G3JA-C437B AC/DC24 Omron, G3JA-C437B AC/DC24 Datasheet
G3JA-C437B AC/DC24
Specifications of G3JA-C437B AC/DC24
G3JAC437BACDC24
Related parts for G3JA-C437B AC/DC24
G3JA-C437B AC/DC24 Summary of contents
Page 1
... Phase reversal detection Current imbalance detection Note: Select either voltage control start or current limit start. Applicable Motors Three-phase, 3-wire Motor Three-phase, 6-wire Motor (Line) (Delta) The G3JA-C can be A 3-phase, 6- used for a 3-phase, wire motor 3-wire motor as (that supports shown in the a star-delta following diagram ...
Page 2
... Production of a new version of the Soft Starter (version 2) with added functions was started in August 2008. The DIP switch settings of the new version are different from the previous version. For details, refer to Upgrades for Version 2 on page 13. When replacing G3JA-C (version 2) with G3JA-D, refer to “Three-phase, 6-wire Motors (Star-delta Wiring)” list above. ■ Accessories (Order Separately) ...
Page 3
... AWG), Stripping length (recommended 5 6 G3JA-C (40°C, Start time Current limit: 350% with fan used) 140 G3JA-C403/C409 120 G3JA-C416/C419 100 G3JA-C425/C430/C437 Load current (A) Model G3JA-C403 G3JA-C409 G3JA-C416 G3JA-C419 G3JA-C425 G3JA-C430 G3JA-C437 Rated breaking current Rated breaking current cULus (UL 508) G3JA-C G3JA-C425 G3JA-C430 G3JA-C437 8 12 ...
Page 4
... A at 120 VAC, 0 240 VAC Open Close: 432 VA cULus (UL 508) cULus (UL 508) 2 peak Hz, 0.19-mm single amplitude 2 peak Hz, 0.075-mm single amplitude 2 ( (15 G) G3JA-C IEC (EN/IEC 60947-4-2) III (See note.) IEC (EN/IEC 60947-4- 2,000 VAC III (See note.) AC15 IEC (EN/IEC 60947-4-2) IEC (EN/IEC 60947-4-2) 4 ...
Page 5
... Applicable Standards Safety standards UL 508 (Listing: File No. E64562), CSA 22.2 No. 14, EN/IEC 60947-4-2 cULus (UL 508) cULus (UL 508) --- --- 4 kV contact discharge and 8 kV air discharge --- --- --- G3JA-C IEC (EN/IEC 60947-4-2) IEC (EN/IEC 60947-4-2) Class A Class A Conforms to IEC 60947-4-2 Conforms to IEC 60947-4-2 Conforms to IEC 60947-4-2 5 ...
Page 6
... E-stop Normal Up-to-speed *1. This transformer is used to convert the load voltage into the control voltage of the G3JA. A transformer is not required if the load voltage is within the rated operational voltage range of the G3JA. *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta). L3 ...
Page 7
... Up-to-speed *1. This transformer is used to convert the load voltage into the control voltage of the G3JA. A transformer is not required if the load voltage is within the rated operational voltage range of the G3JA. *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta). 3 ...
Page 8
... If the motor load is extremely small, the soft stop time will be very short. G3JA-C Kick start (when selected) *2 100% Stable ...
Page 9
... LED indicator and closes the alarm contact. Shorted SCR The G3JA-C always checks the SCR for a short circuit before the starting sequence short circuit is found, the G3JA-C stops the starting sequence, indicates the short circuit with a flashing LED indicator, and closes the alarm contact ...
Page 10
... Note: Test Mode for overload testing will be entered when the Reset Button is pressed for approximately seconds. Test Mode will be cancelled when the Reset Button is pressed again. Control Terminals The G3JA-C has eight input terminals on the front. Each terminal is described in the following table. Description Terminal A1 ...
Page 11
... DIP switch pins Time (seconds OFF OFF OFF ON OFF 0.5 OFF ON 1 1.5 * Set Kick Start to OFF if the G3JA is used with a Current Limit Start. Auxiliary Contacts and Optional Auxiliary Contact Block DIP switch Optional pin 14 Auxiliary Auxiliary contacts Contact (13 to 14) Block (23 to 24) ON ...
Page 12
... Mounting Dimensions for the Auxiliary Contact Block and Round Terminal Block Adapter Trip Class 15 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) 44.8 109 141.5 10 44.8 109 23 141.5 23 G3JA-C Trip Class 20 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) (Unit: mm) Panel Cutouts 4.5 dia 46.4 132 35 3 46.4 ...
Page 13
... Soft start time settings ■ Identifying Upgraded Models You can check whether the G3JA is an upgraded version by the markings on the G3JA or the label on the box. If the G3JA is not marked “Ver. 2,” the previous version. Markings on Unit Comparison of DIP Switch Settings DIP ...
Page 14
... OFF 3. Motor Wiring Method (New Version) Optional Auxiliary Contact Block (Previous Version) Previous version DIP switch pin 15 Optional Auxiliary Contact Block ON (23 to 24) Normal OFF Up-to-speed G3JA-C New version (version 2) DIP switch pins Time (unit OFF OFF OFF OFF ON OFF 10 ON ...
Page 15
... Mounting 1. Mount the fan so that the arrow on the surface of the Fan (G32J- CF64 the direction shown in the figure. 2. Insert the fan connector into the G3JA connector until it clicks into place Mount the fan on the G3JA. Round Terminal Block Adaptor ...
Page 16
... If voltage is applied to the main circuit power supply side of the G3JA, there will be voltage in the terminals on the main circuit load side even if the G3JA is OFF. Be sure to use the warning labels included with the product to provide notification of this hazard on locations such as the motor terminal box, G3JA, and control panel. ...
Page 17
... Connecting a Power Capacitor If you use a power capacitor, connect it to the primary side (i.e., power supply side) of the G3JA output terminals. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. ...
Page 18
... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...