RPC2415 Crydom Co., RPC2415 Datasheet

RELAY PWR CNTRLR 15A 240VAC 1MEG

RPC2415

Manufacturer Part Number
RPC2415
Description
RELAY PWR CNTRLR 15A 240VAC 1MEG
Manufacturer
Crydom Co.
Series
RPCr
Datasheets

Specifications of RPC2415

Load Current
15A
Circuit
SPST-NO (1 Form A)
Output Type
AC, Resistance Controlled
Voltage - Load
200 ~ 240 V
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Package / Case
Hockey Puck
Relay Terminals
Screw Clamp
Peak Surge Current
150A
Load Voltage Max
240VAC
Load Voltage Min
200VAC
Output Voltage Min
200VAC
Input Current Min
0.7A
Load Current Rms Max
15A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Voltage - Input
-
On-state Resistance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
CC1349

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
RPC2415
Manufacturer:
CRYDOM
Quantity:
63
1) All parameters at 25°C unless otherwise specified.
2) Off-State dv/dt test method per EIA/NARM standard RS-443
RPC Series
PRODUCT SELECTION
Description
120 VAC
240 VAC
480 VAC
OUTPUT SPECIFICATIONS (voltage) (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2)
Snubber (Internal)
OUTPUT SPECIFICATIONS (current) (1)
Description
Maximum Load Current [Arms] (3)
Minimum Load Current [mArms]
Maximum Surge Current (16.6ms) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum I²t for Fusing (8.3 msec) [A² sec]
INPUT SPECIFICATIONS (1)
Description
Variable Resistor Size (4)
GENERAL SPECIFICATIONS
Description
Minimum Power Factor (with Maximum Load)
Dielectric Strength, Input/Output/Base (50/60Hz)
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Encapsulation
Terminals
Recommended Terminal Screw Torque Range:
GENERAL NOTES
• Proportional controller
• Ratings from 15A to 40A @ 480 VAC
• 500k or 1M Ohm potentiometer control
• For use with resistive loads only
4) Potentiometer should be line voltage rated.
3) Heat sinking required, see derating curves.
RPC12XX
120 VAC
150K (1W)
RPC1215
RPC2415
RPC4815
90-130
15 A
15 A
5000
1.48
400
150
yes
1.6
10
15
70
94
Screws and saddle Clamps Furnished, Unmounted
8-32 and 10-32 Screws -20 in. lbs.
Thermally conductive Epoxy
(Screws dry without grase)
RPC24XX
240 VAC
6-32 Screws -10 in lbs.
1M (1/2W)
RPC1225
RPC2425
RPC4825
200-240
25 A
25 A
1.02
600
500
yes
250
260
1.6
25
80
-40 to 125 °C
7
-30 to 80 °C
3.2 oz (90g)
2500 Vrms
0.6
RPC48XX
480 VAC
1M (1/2W)
RPC1240
RPC2440
RPC4840
400-480
40 A
40 A
1200
1620
0.63
500
625
1.6
no
40
90
3

Related parts for RPC2415

RPC2415 Summary of contents

Page 1

... Off-State dv/dt test method per EIA/NARM standard RS-443 • Proportional controller • Ratings from 15A to 40A @ 480 VAC • 500k or 1M Ohm potentiometer control • For use with resistive loads only 15 A RPC1215 RPC2415 RPC4815 120 VAC 90-130 400 10 5000 yes ...

Page 2

MECHANICAL SPECIFICATIONS THERMAL DERATE INFORMATION PERCENTAGE ON VS INPUT RESISTANCE AGENCY APPROVALS Rev. 032111 ...

Page 3

...

Page 4

ANNEX - ENVIROMENTAL INFORMATION ...

Related keywords