H3CR-A8 AC100-240/DC100-125 Omron, H3CR-A8 AC100-240/DC100-125 Datasheet - Page 17

RELAY ANALOG SET DPDT 8PIN

H3CR-A8 AC100-240/DC100-125

Manufacturer Part Number
H3CR-A8 AC100-240/DC100-125
Description
RELAY ANALOG SET DPDT 8PIN
Manufacturer
Omron
Series
H3CR-Ar
Datasheet

Specifications of H3CR-A8 AC100-240/DC100-125

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 240VAC
Voltage - Supply
100 ~ 240VAC, 100 ~ 125VDC
Mounting Type
Socket
Termination Style
8 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3CR-A8-AC100240/DC100125
H3CRA8AC100240DC100125
Z2379
2. Signal Start/Signal Reset (in B Mode)
If there is an abnormal signal, flashing starts. When the abnormal
condition is restored, a reset signal stops the display flashing.
C Mode: Signal ON/OFF-delay
The Signal ON-/OFF-delay operation (C mode) is useful for the
control of distribution of products on a production line into boxes by
the specified number or time.
1. Power-ON Start/Instantaneous Operation/
A set of these functions is useful for the operation of a machine for a
specified period when power is ON.
Control output: NC (8 and 11)
Control output: NO (9 and 11)
Control output: NC (8 and 11)
Control output: NO (9 and 11)
Time-limit Reset
Power (2 and 10)
Power (2 and 10)
Reset (2 and 7)
Power indicator
Start (2 and 6)
Start (2 and 6)
NC (1 and 4)
NO (1 and 3)
NC (1 and 4)
NO (1 and 3)
Externally short-circuited
Start signal
Reset signal
Lit
(Power continuously supplied)
Power
supply
Power
supply
Flashing
t
t
Lit
2. Signal-ON-OFF Start/Instantaneous
D Mode: Signal OFF-delay
Signal OFF-delay operation (D mode) can be effectively used to keep
a load operating for a certain period. For example, this function
enables the cooling fan for a lamp or heater to operate for a certain
period after the lamp or heater is switched OFF.
1. Power-ON Start/Instantaneous Operation/
Control output: NC (8 and 11)
Control output: NO (9 and 11)
Control output: NC (8 and 11)
Control output: NO (9 and 11)
Operation/Time-limit Reset
Time-limit Reset
Power (2 and 10)
Power (2 and 10)
Power indicator
Power indicator
Start (2 and 6)
Start (2 and 6)
NC (1 and 4)
NO (1 and 3)
NC (1 and 4)
NO (1 and 3)
Start signal (NC to NO)
Start signal
(The operation starts with the signal ON or OFF)
(Power continuously supplied)
Lit
Power
supply
Power
supply
Flashing
H3CR-A
Lit
17

Related parts for H3CR-A8 AC100-240/DC100-125