ACF-3000AK Amprobe, ACF-3000AK Datasheet - Page 21

FLEX CURRNT TRANSDUCER 3000A

ACF-3000AK

Manufacturer Part Number
ACF-3000AK
Description
FLEX CURRNT TRANSDUCER 3000A
Manufacturer
Amprobe
Type
AC Clampr
Datasheet

Specifications of ACF-3000AK

Style
Flexible Ring
Ac Current Range
30 ~ 3000A
Bandwidth
20kHz
Cable Length
78.740" (2000.00mm)
Max Conductor Size
7.000" (177.80mm)
Termination
Banana Plug, Double, Sheathed
Ratings
CAT III 600V
Frequency Max
20kHz
Length
116mm
Frequency Min
10Hz
Operating Frequency Range
10Hz To 20kHz
Current Measuring Range
30A/300A/3000A
Frequency Measuring Range
10Hz To 20kHz
Accessory Type
AC Current Probe
Sensor Operating Frequency
10Hz To 20kHz
Rohs Compliant
NA
Accuracy
± 1% Of Range
Accuracy %
1%
Battery Size Code
AA
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
For Use With
DMM, Oscilloscope, Recording Instruments
Lead Free Status / RoHS Status
na, Contains lead / RoHS compliant by exemption
Other names
2732388
Caractéristiques techniques
Boîtier
Matériau
Lignes de sortie
Poids
Sécurité
Tension d’essai :
CEM
Dimensions
Tête de mesure
Longueur du câble
Diamètre du câble
Rayon de courbure
minimum
Câble de liaison
Diamètre du
connecteur.
Matériau
Température
de service
Température
de stockage
Poids
Sécurité
IP5X autoextinguible selon UL94-VO
Valox 357 X
prises de sécurité 4-mm
0,19 kg (0,4 livre)
BS EN 61010-1: 1993, 600V CAT III Pol. Deg 2
5550 V AC pendant 1 minute, isolation double
EN 61326 : 1998
116 (L) x 68,5 (l) x 30 (H) mm
4,57 x 2,71 x 1,18 pouces
610 mm (24 pouces), isolation double
14,3 mm (0,562 pouce)
38,1 mm (1,5 pouce)
longueur 2 m (78,7 pouces)
22,2 mm (0,875 pouce)
caoutchouc TPE, polypropylène, en conformité avec les
normes UL94-VO
-20 C à +90 C (-4 F à 194 F)
-40 C à +105 C (-40 F à 221 F)
0,18 kg (0,4 livre)
BS EN 61010-1 : 1993, 600V CAT III Pol. Deg 2
5