ATR20-A-63S-WB2-B-15.0A-2 Sensata Technologies/Airpax, ATR20-A-63S-WB2-B-15.0A-2 Datasheet

CIRCUIT BREAKER THERM 15A

ATR20-A-63S-WB2-B-15.0A-2

Manufacturer Part Number
ATR20-A-63S-WB2-B-15.0A-2
Description
CIRCUIT BREAKER THERM 15A
Manufacturer
Sensata Technologies/Airpax
Series
ATR20r

Specifications of ATR20-A-63S-WB2-B-15.0A-2

Breaker Type
Thermal
Voltage
50VDC, 125/250VAC
Current - Trip (it)
15A
Number Of Poles
1
Actuator Type
Push to Reset
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
723-1147
ATR20-A-63S-WB2-B-.0A-2
306
featUReS
• RoHS compliant, single pole, thermal current overload protector
• Reliable, trip-free operation on current overloads
• Warranty: 24-months from date of manufacture
DeScRiption
The Airpax™ ATR20 product family is a single pole, thermally operated overload protector with a snap-acting trip mechanism that
provides reliable, trip-free operation on current overloads. The ATR20 series is designed with multiple mounting configurations
including central nut and wing clip.
SpecificationS
Conditional Short Circuit Capacity
Rated Short Circuit Capacity Icn
ATR20 Series
Overload Switching Capacity
Max Operating Temperature
Tripping Current Code (TC)
Standard Current Ratings
Initial Withstand Voltage
Inc1 (PC1) per EN 60934
Max Breaking Capacity
Insulation Resistance
Applicable Approvals
Dielectric Strength
Method of Tripping
Type of Actuation
Application Type
Overload Rating
Operational Life
Voltage Ratings
Ref. EN 60934
Weight
Thermal Circuit Protector for Equipment
2.5, 3, 4, 5, 6, 7, 8, 10, 12, 15, 16, 20 Amps (AC - inductive, DC - resistive)
1000A 125 / 250VAC, 50VDC,SC:1kA, C1, 125 / 250VAC, 50VDC
Min. 6 X Rated Current (6 X In), 250VAC inductive
Min. 4 X Rated Current (4 X In), 50VDC resistive
OL0 240Vac, 50Vdc, ref: CSA22.2, No. 235-04
UL 1077, CSA 22.2 No. 235-04, TÜV EN 60934
General Industrial ref: CSA22.2, No. 235-04
6x I
• Protection range and operating voltage:
Ref. CSA 22.2 No. 235-04, UL 1077
125 / 250 VAC, 50/60 Hz, 50 VDC
1.5 KV for 1 min. (per EN60934)
0.1 to 16.0 Amps, 240 VAC, 50 VDC (cЯUus,cCSAus)
0.5 to 12 Amps, 240 VAC, 24 VDC (VDE)
n
TC2 ref: CSA22.2, No. 235-04
8x I
AC Up to 9A, 4x In DC Up to 12A
Approximately 17 grams
60A Max. from 10A to 12A
Min 100 MΩ @ 500VDC
Thermal “TO”, trip-free
Reset button, type “R”
atR20 Series
n
60°C (140°F) Ambient
2.5 KV (per EN60934)
1000 Cycles @ 2 x I
for < 6A, 60A max. > 6A
n
http://airpax.sensata.com/

Related parts for ATR20-A-63S-WB2-B-15.0A-2

ATR20-A-63S-WB2-B-15.0A-2 Summary of contents

Page 1

... Warranty: 24-months from date of manufacture DeScRiption The Airpax™ ATR20 product family is a single pole, thermally operated overload protector with a snap-acting trip mechanism that provides reliable, trip-free operation on current overloads. The ATR20 series is designed with multiple mounting configurations including central nut and wing clip. ...

Page 2

... Recommended Rating: 5.0 x 1.1 = 5.5 Select the Nearest Rating = 6.0 amps (nearest) http://airpax.sensata.com 0.6 0 0.85 0.9 0 0.85 0.88 0.9 Operating Characteristics : 1000 100 10 1 0.1 0 100 + 0 1 1.1 1.3 1.4 200 300 400 500 600 700 800 900 1000 135 CURRENT (%) ATR20 Series 307 ...

Page 3

... ATR20 Series Panel cutout .378 -.004 ( ) Ø 9.6 -0.1 3/8" - 27UNS Pitch Panel cutout M11X1 +.008 .441 ( ) Ø Pitch 11.2 +0 ...

Page 4

... Mounting Nuts PLASTIC VERTICAL KNURLED NUT (P/N 053-200-0001) Panel Cutout 15 Positions HORIZONTAL 15 Panel Cutout Positions DeciSion tabLeS ATR20 - 7. Product Type 2 Mounting Bushing A Plastic 3/8”-27 C Plastic M11 W Wing Clip 3 Terminal Size 63 .250 http://airpax.sensata.com/ L. 90° BEND, LEFT SIDE .343 8 ...

Related keywords