Specifications of AC2-B0-46-625-4F4-C

Breaker Type
Hydraulic-Magnetic
Voltage
80VDC, 277VAC
Current - Trip (it)
25A
Number Of Poles
2
Actuator Type
Rocker
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
AC2-B0-46-625-2F4-C
AC2-B0-46-625-2F4-C
Q3851774
36
A-Series – General Specifications
Notes for Table B:
1
2
3
4
Table C:
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classified Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
Notes for Table C:
1
2
Table D:
(Guide DITT, File E189195), under UL489A.
Notes for Table C:
1
Electrical
Table B:
Supplementary Protector.
CONFIGURATION
CIRCUIT
SERIES
General Purpose Ratings for UL/CSA Only.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
Same as note 2, except that backup fuse is limited to 80 A maximum.
Meets the requirements of CSA 22.2 No. 100-04 - Motors and Generators.
Available with special catalog number only (consult factory).
2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System.
Parallel Pole Construction
Lists UL Recognized, CSA Accepted configurations and performance capabilities as Protectors, Supplementary for
Lists UL Listed configurations and performance capabilities as Circuit Breakers for use in Communications Equipment
Lists UL Recognized, CSA Accepted, VDE & TUV Certified configurations & performance capabilities as a Component
125 / 250
RATING
MAX.
250
14
32
65
1
1
A-SERIES TABLE C: UL1500 (Marine Ignition Protected)
FREQUENCY
VOLTAGE
50 / 60
50 / 60
DC
DC
DC
PHASE
---
---
---
1
1
2
CURRENT
FULL LOAD
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 50
0.02 - 30
RATING
AMPS
SHORT CIRCUIT
BACKUP FUSE
CAPACITY
WITHOUT
(AMPS)
5000
5000
3000
1500
1000
TC1,2,OL1,U1 TC1,2,OL1,U1
TC1,2,OL1,U2 TC1,2,OL1,U2
TC1,2,OL1,U1 TC1,2,OL1,U1
TC1,2,OL1,U1 TC1,2,OL1,U1
TC1,2,OL1,U1 TC1,2,OL1,U1
APPLICATION CODES
UL
CSA
www.carlingtech.com