BK/SC-25 Cooper/Bussmann, BK/SC-25 Datasheet

no-image

BK/SC-25

Manufacturer Part Number
BK/SC-25
Description
FUSE 25A 480V T-LAG UL CSA
Manufacturer
Cooper/Bussmann
Series
SCr
Datasheet

Specifications of BK/SC-25

Fuse Type
Slow Blow, Time Lag
Voltage - Rated
480VAC, 300VDC
Current
25A
Package / Case
Cylindrical
Size / Dimension
0.406" Dia x 1.620" L (10.30mm x 41.15mm)
Mounting Type
Holder
Color
-
Operating Temperature
-
Dc Cold Resistance
-
Melting I²t
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Operating Temperature
-
Color
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
BK-SC-25
Catalog Symbol: SC
Current-Limiting
Ampere Rating: ⁄Ω™ to 60A (fast-acting),
7 to 60A (time-delay)
Voltage Ratings:
SC ⁄Ω™ to 20
SC 25 to 60
Interrupting Rating: 100,000A RMS Sym. AC, 10,000A dc
Agency Information:
UL Listed, Std. 248-5, Class G, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.5, Class 1422-01, File 53787
Catalog Numbers
SC-⁄Ω™
SC-1
SC-1⁄Ω™
SC-2
SC-2⁄Ω™
SC-3
SC-4
SC-5
Carton Quantity and Weight
Catalog
Number
⁄Ω™–15
20
25–30
35–60
†Weight per carton.
0104
Time-Delay Fuses
Class G – 600 Volt,
© 2011 Cooper Bussmann
www.cooperbussmann.com
SB04105
Carton
480 Volt, 25 - 60 Amps
Qty.
600Vac, 170Vdc
480Vac, 300Vdc
4
4
2
2
SC-6
SC-7
SC-8
SC-9
SC-10
SC-12
SC-15
SC-20
1
2
0.060
0.064
0.040
0.075
Lbs.
- 20 Amps
Weight†
SC-25
SC-30
SC-35
SC-40
SC-45
SC-50
SC-60
0.0272
0.029
0.018
0.0340
Kg.
Fuse (Amps)
SC-⁄Ω™ to 15
SC-20
SC-25 to 30
SC-35 to 60
General Information:
• Compact branch-circuit units with high interrupting rating
• With 600V rating, they can be used in 120/208, 120/240
• Length variations relative to case size make the “rejec-
• In general, SC fuses are about ⁄Ω£ the size of the 600V
• SC fuses with ampere ratings above 6A have a
Dimensional Data
and current-limitation.
and 277/480V circuits.
tion” type fuses.
NEC fuse type.
degree of overload time-delay which permits them to
pass temporary overloads. At 200% load, they have a
minimum opening time of 12 seconds.
Page 1 of 3
Bussmann Application Engineering at 636-527-1270 for more information.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
(Length)
A
.41"
(10.41mm)
Class G fuses
See Data Sheets listed below
Recommended fuseblocks/fuseholders for
• Open fuseblocks - 1106
• In-line fuseholders - 1123, 1124
Data Sheet 1024
1.31∑
1.41∑
1.62∑
2.25∑
A
SC

Related parts for BK/SC-25

BK/SC-25 Summary of contents

Page 1

... With 600V rating, they can be used in 120/208, 120/240 and 277/480V circuits. • Length variations relative to case size make the “rejec- tion” type fuses. • In general, SC fuses are about ⁄Ω£ the size of the 600V SC-25 NEC fuse type. SC-30 • ...

Page 2

Peak Let-Through Curves 10,000 1,000 A 100 RMS SYMMETRICAL CURRENTS IN AMPERES A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 X SYMM RMS AMPS) © 2011 Cooper Bussmann www.cooperbussmann.com 0104 SB04105 B Page Data Sheet 1024 ...

Page 3

Time-Current Characteristic Curves– Total Clearing 300 100 . The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are ...