2866983 Phoenix Contact, 2866983 Datasheet - Page 2

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
MINI-SYS-PS-100-240AC/24DC/1.5
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866983
The electronic short-circuit and idling-proof device is connected to single-phase AC networks with nominal voltages of
100 V AC to 240 V AC or to two of the phase conductors of three-phase networks with a linked voltage of this value. In
the event of a malfunction, the output voltage is limited to 30 V DC.
Due to the U/I characteristic curve with POWER BOOST, miniature circuit breakers blow reliably. For function monitoring,
there is the floating DC OK output and the DC OK LED. High operational reliability is provided by the mains failure
bridging time of more than 20 ms under full load.
Ambient temperatures can be in the range of -25°C to +70°C, whereby the power reserve of approx. 25% up to 40°C is
permanently available.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Technical data
Input data
Nominal input voltage
AC input voltage range
AC frequency range
Current consumption
Inrush surge current
Power failure bypass
Input fuse
Permissible backup fuse
Type of protection
Protective circuit/component
Output data
Nominal output voltage
Output current
Derating
Connection in parallel
Connection in series
Max. capacitive load
Order No.: 2866983
100 V AC ... 240 V AC
85 V AC ... 264 V AC
45 Hz ... 65 Hz
Approx. 0.75 A (120 V AC)
0.45 A (230 V AC)
< 15 A (0.6 A
> 35 ms (120 V AC)
> 150 ms (230 V AC)
3.15 A (slow-blow, internal)
B6
B10
B16
Transient surge protection
Varistor
24 V DC ±1%
1.5 A (-25 °C ... 60 °C)
2 A (with POWER BOOST, -25°C ... 40°C permanent)
from +60 °C to +70 °C: 2.5% per Kelvin
60 °C ... 70 °C (2.5%/K)
Yes, for redundancy and increased capacity.Maximum of 2
devices for redundancy on DIN rail connector.
No
Unlimited
2
s)
Oct 8, 2010
Page 2 / 7