ACM20-2-AC1-R-C Murata Power Solutions Inc, ACM20-2-AC1-R-C Datasheet

Digital Panel Meters 10A 85-264Vac Supply Power Factor Reading

ACM20-2-AC1-R-C

Manufacturer Part Number
ACM20-2-AC1-R-C
Description
Digital Panel Meters 10A 85-264Vac Supply Power Factor Reading
Manufacturer
Murata Power Solutions Inc
Type
AC Power Metersr
Datasheet

Specifications of ACM20-2-AC1-R-C

Equipment Type
AC Power Meters
Input
10 A
Display Type
4 Digit LCD
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Actual size
FEATURES
www.murata-ps.com
SIMPLIFIED SCHEMATIC DIAGRAM
Displays AC Volts, Amps, Watts, and Power Factor or Hertz
Two display modes: continuous auto cycling or fi xed
Universal 85-264Vac (47-63Hz) operating range
(Measurement Category II)
Built-in current transformers simplify installation; choice of
10A, 32A, or 100A ranges
Ideal for power distribution units (PDUs) and power strips
True-rms readings of complex voltage and current waveforms
Low-power consumption: less than ¼watt from 120Vac
One-piece polycarbonate housing fi ts ‘0U’ & ‘1U’ racks
Surface mount design occupies minimal panel space
Bright red LED-display with four annunciators
Optional Frequency reading models (0.1Hz resolution)
Approvals to UL/CSA/IEC/EN 61010-1
www.murata-ps.com/rohs
For full details go to
 
C
®
85-264 Vac
47-63 Hz
US E156931
B
A
LOAD CURRENT
www.murata-ps.com/dpm
L1
Murata Power Solutions’ ACM20 series AC power meters display the most critical measure-
ments in mains-powered equipment: voltage, amperage, active power (watts), and power
factor. A front panel selector-switch provides two modes of operation: a fi xed reading of
any of the four parameters, or a continuous cycling through all four measurements. An
optional model displays line frequency with 0.1Hz resolution. All ACM20 multi-function
power meters include built-in current transformers—no other user-supplied components
are required.
ACM20 series AC power meters are available in a choice of three input ranges: 0-10A (with
0.001A resolution, 999.9 watts max.); 0-32A (with 0.01A resolution, 9999 watts max.); and
0-100A (0.1A resolution, 26.4kW max.). An 85-264Vac (47-63Hz) operating supply range
makes these power meters perfect for worldwide power monitoring applications. And,
unlike conventional, average-responding products, ACM20 power meters can accurately
display the real power and true-rms current values of triangle waves, square waves, and
other irregularly shaped waveforms, with a typical accuracy of ±1% of full scale.
Their large (0.36"/9.2mm), bright red LED display makes ACM20 AC power meters easily
readable from as far as 15 feet (5 meters). All units are packaged in a one-piece, vibration
resistant, polycarbonate housing that can be installed in vertical ‘0U’ and ‘1U’ rack spaces.
Their miniature size is perfect for UPS power sources, power strips, laboratory instrumenta-
tion, alternative energy applications, and any other products that require precise monitoring
of AC power.
PRODUCT OVERVIEW
+5V
CONVERTER
CONVERTER
VOLTS
AC/DC
A/D
AMPS
+5V
WATTS
PF
+5V
03 Mar 2011 MPM_ACM20 Series.A09 Page 1 of 6
Four-Function AC Power Meters
CONTROLLER
MICRO-
SEL
ACM20 Series
email: sales@murata-ps.com

ACM20-2-AC1-R-C Summary of contents

Page 1

... ACM20 series AC power meters are available in a choice of three input ranges: 0-10A (with 0.001A resolution, 999.9 watts max.); 0-32A (with 0.01A resolution, 9999 watts max.); and 0-100A (0.1A resolution, 26.4kW max.). An 85-264Vac (47-63Hz) operating supply range makes these power meters perfect for worldwide power monitoring applications ...

Page 2

... All specifi ed maximum supply currents are steady state; larger surge currents can occur at initial application of line power. ➄ Applies to 10A and 32A models only. Typ. Max. Units ORDERING INFORMATION - 264.0 Volts ACM20-2-AC1-R-C - 9.999 Amperes ACM20-5-AC1-R-C - 32.00 Amperes - 100.0 Amperes ...

Page 3

... ACM20 power meter’s internal components (printed circuit board, resistor, capacitors, current transformer L1’s secondary leads, etc.) are at the ac-mains potential connected to TB1. ACM20 power meters are designed to measure and be powered from one ac power-source only. Any other connection schemes will introduce signifi cant mea- surement errors ...

Page 4

... Figure 4. Wiring diagram for 220/240V systems with neutral (monitoring L2) www.murata-ps.com/dpm ACM20 Series Four-Function AC Power Meters 220 V LOAD L2 220 V LOAD Fuse* Fuse* email: sales@murata-ps.com 03 Mar 2011 MPM_ACM20 Series.A09 Page TB1 A *See technical note 5. B TB1 A *See technical note 5. TB1 B A *See technical note 5. ...

Page 5

... PANEL INSTALLATION All connections to ACM20 power meters must be made after the unit is securely attached to the panel and with all associated load and supply voltages de energized (off), using extreme caution and observ- ing all safety measures applicable to the user’s installation. Care should be exercised when passing conductors through the power meter’ ...

Page 6

... Bottom View OSCILLOGRAMS The graphs below show typical ACM20 power meter VOLTS readings when the unit is powered from four common ac-voltage waveforms. Murata Power Solutions, Inc. 11 Cabot Boulevard, Mansfi eld, MA 02048-1151 U.S.A. ISO 9001 and 14001 REGISTERED Dimensions are in inches (mm). ...