Specifications of UPG66-1-61-303-01

Breaker Type
Hydraulic-Magnetic
Voltage
65VDC, 250VAC
Current - Trip (it)
30A
Number Of Poles
1
Actuator Type
Toggle
Mounting Type
Panel Mount
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
Q5847328
T1400143
Introduction
Single & Multi-Pole
Rocker, Sealed Toggle
Configurations
Operating Characteristics
Delay Curves
Specifications
Decision Tables
|
|
|
|
|
|
|
|
120
121
124
129
131
132
136
138
APG/UPG/IPG Series
Magnetic Circuit Protectors

Related parts for UPG66-1-61-303-01

UPG66-1-61-303-01 Summary of contents

Page 1

Introduction Single & Multi-Pole Rocker, Sealed Toggle Configurations Operating Characteristics Delay Curves Specifications Decision Tables APG/UPG/IPG Series Magnetic Circuit Protectors 120 | 121 | | 124 | 129 131 | 132 | | 136 | 138 ...

Page 2

... INTRODUCTION The APG/UPG magnetic circuit protector provides low-cost power switching, reliable circuit protection and accurate circuit control in one complete package intended for use in data processing and broadcast equipment, vending and amusement machines, military and marine applications, and wherever precision operation is required. ...

Page 3

APG/UPG SINGLE POLE CIRCUIT PROTECTORS Single Pole, Toggle 1.640 [ 41.66 ] Single Pole .590 DIA. MAX. [ 15.00 ] 2.00 OFF [ 50.80 ] 1.22 [ 31.00 ] .75 [ 19.05 ] Single Pole, Mounting Detail +.010 -.000 2X ...

Page 4

TwO POLE PROTECTORS An assembly consisting of two single pole units, having their trip mechanisms internally coupled, and with a single toggle handle, forms the APG/UPG-11 also possible to provide a handle per pole, which is referred to ...

Page 5

THREE POLE AND FOUR POLE PROTECTORS The three pole structure consists of three single pole units assembled with an internal mechanical interlock which actuates all units simultaneously. A single toggle handle operates all three poles handle per pole ...

Page 6

APGHX / UPGHX Rocker actuated APGHX/UPGHX provides one rocker handle for each pole of a multi-pole circuit protector. .23 [ 5.84 ] 2.00 1.22 [ 50. 31.00 ] 1.53 [ 38.86 ] .340 1.640 [ 41. ...

Page 7

APGX / UPGX Rocker actuated APGX / UPGX provides one rocker handle per circuit protector. .23 [ 5.84 ] 2.00 1.22 [ 50. 31.00 ] 1.53 [ 38.86 ] 1.640 [ 41.66 ] Three Pole 2.265 MAX. [ ...

Page 8

... BAT HANDLE / PANEL SEAL (APGN / UPGN) The APGN is designated to provide circuit protection in harsh and military environments. Waterproof panel integrity is provided by an “O” ring bushing seal and silicon rubber gland within the bushing/ handle assembly. Single, two or three pole versions are available with two and three pole versions featuring a single operating handle and mounting bushing ...

Page 9

Standard Handle Location (Applies to 2 Pole Only) Toggle Handles OFF APG/UPG Bat Handle/ Panel Seal APGN/UPGN Rocker ON OFF APGX/UPGX http://airpax.sensata.com/ TOGGLE HANDLES (APG/UPG) The APG/UPG circuit protector is available with toggle handles in six different col- ors. For ...

Page 10

IPG MAGNETIC CIRCUIT PROTECTORS The IPG circuit protectors provide the advantages of magnetic “stand alone” protection and compliance with UL, CSA, SEV, VDE and IEC standards. They are UL Recognized per UL STD. 1077 as supplementary protectors, CSA Certified per ...

Page 11

Series and Switch Only .23 [ 5.84 ] 1.53 [ 38.86 ] Series Switch Only Shunt and Dual Coil .23 [ 5.84 ] 1.53 [ 38.86 ] 1.38 [ 35.05 ] Shunt Dual Coil Tapped Coil .23 [ 5.84 ] ...

Page 12

Relay Trip This permits the overload sensing coil to be placed in a circuit which is electrically isolated from the trip contacts. The coil may be actuated by sensors monitoring pressure, flow, temperature, speed, etc. Other typical applications include crowbar, ...

Page 13

APG/UPG/IPG OPERATING CHARACTERISTICS NOMINAl DCR / IMPeDANCe Resistance (ohms) Current DC Delays Ratings (Amps 51, 52, 53 0.05 162 540 460 0.10 35.4 105 155 0.50 1.2 4.2 4.5 1.0 .236 1.02 1.2 5.0 .021 .048 .059 10.0 ...

Page 14

DUAl fReQUeNCY (50/60Hz) PeRCeNTAGe Of RATeD CURReNT VS TRIP TIMe IN SeCONDS AT +25°C Delay 100% 135 Trip . Trip 7 to 130 73 No Trip 50 to 700 Notes: All trip curves and ...

Page 15

PERCENT OF RATED CURRENT 10000 1000 100 .01 .001 0 100 150 200 300 400 125 PERCENT OF RATED CURRENT http://airpax.sensata.com/ DELAY ...

Page 16

DC Delay Curves (typ) 10000 DELAY 50 1000 100 .01 .001 0 100 150 200 300 400 500 600 125 PERCENT OF RATED CURRENT 10000 DELAY 51 1000 100 .01 .001 0 100 150 ...

Page 17

Delay Curves (typ) 10000 1000 100 .01 .001 0 100 150 200 300 400 125 PERCENT OF RATED CURRENT 10000 1000 100 .01 .001 0 100 150 200 300 400 125 PERCENT OF ...

Page 18

Trip free will trip open on overload, even when forcibly held in the ON position. Trip Indication The operating handle moves positively to the OFF position on overload. Ambient Operation APG/UPG protectors operate normally in temperatures between –40°C and +85°C. ...

Page 19

Moisture Resistance Meets all the requirements of MIL-PRF-55629 when tested in accordance with Method 106 of MIL-Std. 202. Salt Spray (Corrosion) Meets requirements of MIL-PRF-55629 when tested in accordance with Method 101 of MIL-Std. 202. All APG/UPG protectors are constructed ...

Page 20

APG / UPG Decision Table - How to Order The ordering code for APG/UPG circuit protectors may be determined by following the steps in the decision tables shown here. The coding given permits a self-assigning part number but with certain ...

Page 21

Third Decision Internal Configuration Switch only (omit 4th and -0 5th decisions) -1 Series -1REC4 Auxiliary switch* .110 quick-connect -1REG4 Auxiliary switch* (Gold Contacts) .110 quick-connect -1REC5 Auxiliary switch* .187 quick-connect -3 Shunt ( amperes only) -4 ...

Page 22

IPG Decision Table - How to Order The ordering code for IPG circuit protectors may be determined by following the steps in the decision tables shown here. The coding given permits a self-assigning part number but with certain limitations. Units ...

Page 23

Fourth Decision Hz and Delay -40 400Hz 150% instant trip -41 400Hz short delay -42 400Hz long delay -43* 400Hz motor start -49 400Hz 130% instant trip -50 DC 150% instant delay -51 DC short delay -52 DC long ...

Page 24

...

Related keywords