LC1D25U7 SQUARE D, LC1D25U7 Datasheet - Page 3

CONTACTOR 3PST-NO, 240VAC, 40A, DIN RAIL

LC1D25U7

Manufacturer Part Number
LC1D25U7
Description
CONTACTOR 3PST-NO, 240VAC, 40A, DIN RAIL
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D25U7

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Coil Voltage Vac Nom
240V
Width
45mm
Relay Terminals
Screw Clamp
Peak Reflow Compatible (260 C)
No
Operating Voltage
600VAC
Switching Power Ac1
3hp
Switching Power Ac3
20hp
Switching Current Ac1
40A
Switching Current Ac3
25A
Load Current Inductive
25A
Load Current Resistive
40A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Complementary
Environment
Offer Sustainability
Coil technology
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non-overlap time
Insulation resistance
IP degree of protection
Protective treatment
Pollution degree
Ambient air temperature for operation
Ambient air temperature for storage
Permissible ambient air temperature around the de-
vice
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
Height
Width
Depth
Product weight
Sustainable offer status
RoHS
REACh
Product environmental profile
Product end of life instruction
Safety reliability level
Mechanical durability
Operating rate
Without built-in suppressor module
0.85...1.1 Uc at 60 °C operational 60 Hz
0.8...1.1 Uc at 60 °C operational 50 Hz
0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
70 VA at 20 °C (cos ϕ 0.75) 50 Hz
70 VA at 20 °C (cos ϕ 0.75) 60 Hz
7 VA at 20 °C (cos ϕ 0.3) 50 Hz
7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
2...3 W at 50/60 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
25...400 Hz
5 mA for signalling circuit
17 V for signalling circuit
1.5 ms on energisation (between NC and NO contact)
1.5 ms on de-energisation (between NC and NO contact)
> 10 MOhm for signalling circuit
IP2x front face conforming to IEC 60529
TH conforming to IEC 60068-2-30
3
-5...60 °C
-60...80 °C
-40...70 °C at Uc
3000 m without derating in temperature
850 °C conforming to IEC 60695-2-1
V1 conforming to UL 94
Shocks contactor open 8 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms
Vibrations contactor closed 4 Gn, 5...300 Hz
Vibrations contactor open 2 Gn, 5...300 Hz
85 mm
45 mm
92 mm
0.37 kg
Not Green Premium product
Compliant - since 0627 -
Reference not containing SVHC above the threshold
Available
Need no specific recycling operations
download declaration of conformity
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
15 Mcycles
3600 cyc/h at <= 60 °C
3