MY4Z DC24(S) Omron, MY4Z DC24(S) Datasheet - Page 3

POWER RELAY, 4PDT, 24VDC, 5A, PLUG IN

MY4Z DC24(S)

Manufacturer Part Number
MY4Z DC24(S)
Description
POWER RELAY, 4PDT, 24VDC, 5A, PLUG IN
Manufacturer
Omron
Datasheet

Specifications of MY4Z DC24(S)

Relay Type
General Purpose
Coil Voltage Vdc Nom
24V
Contact Current Max
5A
Contact Voltage Ac Nom
250V
Contact Voltage Dc Nom
30V
Coil Resistance
636ohm
Contact Configuration
4PDT
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
■ Characteristics
Note: The values given above are initial values.
■ Life Expectancy Characteristics
■ Approved Standards
VDE, UL, CSA, IMQ, CE
■ Precautions
Connections
Do not reverse polarity when connecting DC-operated Relays with
built-in diodes or indicators or high-sensitivity DC-operated Relays.
Mounting
Whenever possible, mount Relays so that it is not subject to vibration
or shock in the same direction as that of contact movement.
Contact resistance
Operate time
Release time
Max. operating frequency
Insulation resistance
Dielectric withstand voltage
Vibration resistance
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
Weight
Pole
2-pole
4-pole
4-pole (bifurcated)
Mechanical life
(at 18,000 operations/hr)
AC:50,000,000 operations min.
DC:100,000,000 operations min.
20,000,000 operations min.
Mechanical 18,000 operations/hr
Electrical
Operating
Operating
100 mΩ max.
20 ms max.
20 ms max.
1,800 operations/hr (under rated load)
1,000 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Destruction:10 to 55 Hz, 1.0 mm double amplitude
Malfunction:10 to 55 Hz, 1.0 mm double amplitude
Destruction:1,000 m/s
Malfunction:200 m/s
See the following table.
-55°C to 70°C (-67°F to 158°F) with no icing (see note)
5% to 85% RH
Approx. 35 g
2
(approx. 20G)
2
(approx. 100G)
Electrical life
(at 1,800 operations/hr under rated load)
500,000 operations min.
200,000 operations min.
100,000 operations min.
General-purpose Relay
MY
261

Related parts for MY4Z DC24(S)